Page 1: Energy Management :: 2007/2008 - Técnico Lisboa ... · Energy Management Class # 3P :: RGCE – TEP – Specific Energy Consumption Slide 8 of 53 Specific Energy Consumption EXEMPLO

Energy Management :: 2007/2008

Class # 3P

RGCE – TEP – Specific Energy Consumption

Dr. João [email protected]

Page 2: Energy Management :: 2007/2008 - Técnico Lisboa ... · Energy Management Class # 3P :: RGCE – TEP – Specific Energy Consumption Slide 8 of 53 Specific Energy Consumption EXEMPLO

Energy Management

Class # 3P :: RGCE – TEP – Specific Energy Consumption Slide 2 of 53

RGCE

RGCE – Regulamento de Gestão dos Consumos de Energia

A abordagem do RGCE assenta em duas linhas de cálculo fundamentais:

- Os consumos são convertidos em energia primária;- A eficiência energética é feita pelo cálculo dos consumos específicos.

O RGCE aplica-se a:- Instalações com consumo superior a 1000 tep/ano;- Instalações com equipamento cujo consumo total nominal excede 0.5 tep/hora;- Instalações com pelo menos 1 equipamento cujo consumo energético nominal excede 0.3 tep/hora

Regras de cumprimento:

se c > K, então redução de consumo especifico (c) por forma a que no final de 5 anos a diferença entre o valor actual e o valor de consumo especifico de referência (K) seja reduzida a metade do valor inicial (c5 < c0 – (c0-K)/2 = (c0 + K)/2);

se c0 < K, então K=0.9*c0

Page 3: Energy Management :: 2007/2008 - Técnico Lisboa ... · Energy Management Class # 3P :: RGCE – TEP – Specific Energy Consumption Slide 8 of 53 Specific Energy Consumption EXEMPLO

Energy Management

Class # 3P :: RGCE – TEP – Specific Energy Consumption Slide 3 of 53

TEP

TEP como Unidade de Energia Primária

Page 4: Energy Management :: 2007/2008 - Técnico Lisboa ... · Energy Management Class # 3P :: RGCE – TEP – Specific Energy Consumption Slide 8 of 53 Specific Energy Consumption EXEMPLO

Energy Management

Class # 3P :: RGCE – TEP – Specific Energy Consumption Slide 4 of 53

TEP

TEP como Unidade de Energia PrimáriaA Tonelada equivalente de petróleo (tep) é a unidade de energia primária consagrada mundialmente, da mesma forma que em energia final a unidade considerada é o Joule (J).

conversão para tep = (Energia Primária / Energia Final)

Considerando que a tecnologia de referência se baseia no petróleo bruto. Na prática, a tep corresponde a um hipotético petróleo bruto que liberta na sua combustão um calor correspondente a 10 Gcal/ton (41.9 GJ/ton).

Exemplo de coeficientes de conversão para TEP

Electricidade 0.29 kgep/kWh

Thick fuel-óleo 0.969 tep/ton

Propano 1.140 tep/ton

Gás natural 0.82 tep/103 m3

Gasóleo 0.872575 tep/m3

Page 5: Energy Management :: 2007/2008 - Técnico Lisboa ... · Energy Management Class # 3P :: RGCE – TEP – Specific Energy Consumption Slide 8 of 53 Specific Energy Consumption EXEMPLO

Energy Management

Class # 3P :: RGCE – TEP – Specific Energy Consumption Slide 5 of 53

Specific Energy Consumption

EXEMPLO

Fabrica de Vidro

Page 6: Energy Management :: 2007/2008 - Técnico Lisboa ... · Energy Management Class # 3P :: RGCE – TEP – Specific Energy Consumption Slide 8 of 53 Specific Energy Consumption EXEMPLO

Energy Management

Class # 3P :: RGCE – TEP – Specific Energy Consumption Slide 6 of 53

Specific Energy Consumption

EXEMPLO – Fabrica de Vidro

Fusão

Matéria prima

Forno a gás e fusão eléctrica

Fabricação Matéria fundente em peças de cristalArrefecimento

Aquecimento

Recozimento

Roça

Minimização tensões internas

Polimento

Armazém liso

Tratamento final

Armazém produtos

Lapidação, decoração, …

Page 7: Energy Management :: 2007/2008 - Técnico Lisboa ... · Energy Management Class # 3P :: RGCE – TEP – Specific Energy Consumption Slide 8 of 53 Specific Energy Consumption EXEMPLO

Energy Management

Class # 3P :: RGCE – TEP – Specific Energy Consumption Slide 7 of 53

Specific Energy Consumption

Page 8: Energy Management :: 2007/2008 - Técnico Lisboa ... · Energy Management Class # 3P :: RGCE – TEP – Specific Energy Consumption Slide 8 of 53 Specific Energy Consumption EXEMPLO

Energy Management

Class # 3P :: RGCE – TEP – Specific Energy Consumption Slide 8 of 53

Specific Energy Consumption

EXEMPLO – Fabrica de Vidro

Objectivo: Auditoria energética - Quantificação da Intensidade Energética da fábrica de vidro + Verificação cumprimento RGCE.

Intensidade energética -> ?

Consumo especifico (c) [TEP/tonprod]ano

Consumo especifico de referência para um fábrica de vidro (RGCE) – Kvidro = 1100 kgep/ton

Consumo absoluto de energia -> ?

Fornos de fundição – Gás Propano + Electricidade

Page 9: Energy Management :: 2007/2008 - Técnico Lisboa ... · Energy Management Class # 3P :: RGCE – TEP – Specific Energy Consumption Slide 8 of 53 Specific Energy Consumption EXEMPLO

Energy Management

Class # 3P :: RGCE – TEP – Specific Energy Consumption Slide 9 of 53

58%

42%

Gás Propano

Electricidade

Specific Energy Consumption

EXEMPLO – Fabrica de Vidro

Page 10: Energy Management :: 2007/2008 - Técnico Lisboa ... · Energy Management Class # 3P :: RGCE – TEP – Specific Energy Consumption Slide 8 of 53 Specific Energy Consumption EXEMPLO

Energy Management

Class # 3P :: RGCE – TEP – Specific Energy Consumption Slide 10 of 53

Specific Energy Consumption

EXEMPLO – Fabrica de Vidro

Gás propano

Electricidade

Page 11: Energy Management :: 2007/2008 - Técnico Lisboa ... · Energy Management Class # 3P :: RGCE – TEP – Specific Energy Consumption Slide 8 of 53 Specific Energy Consumption EXEMPLO

Energy Management

Class # 3P :: RGCE – TEP – Specific Energy Consumption Slide 11 of 53

Specific Energy Consumption

EXEMPLO – Fabrica de Vidro

O RGCE aplica-se à fábrica de vidro? RGCE aplica-se a instalações com consumo superior a 1000 tep/ano.

Cvidro = 3087 tep/ano

Consumo especifico de referência para um fábrica de vidro (RGCE) – Kvidro = 1100 kgep/ton

- Cumprimento do RGCE

c5 = c0 – (c0-K)/2 = (c0 + K)/2

c0 < K -> K=0.9*c0

C5 = (1072 tep/ton + 0.9*1072 tep/ton)/2

= 1018.4 tep/ton

Page 12: Energy Management :: 2007/2008 - Técnico Lisboa ... · Energy Management Class # 3P :: RGCE – TEP – Specific Energy Consumption Slide 8 of 53 Specific Energy Consumption EXEMPLO

Energy Management

Class # 3P :: RGCE – TEP – Specific Energy Consumption Slide 12 of 53

Specific Energy Consumption

EXEMPLO – Fabrica de Vidro

Page 13: Energy Management :: 2007/2008 - Técnico Lisboa ... · Energy Management Class # 3P :: RGCE – TEP – Specific Energy Consumption Slide 8 of 53 Specific Energy Consumption EXEMPLO

Energy Management

Class # 3P :: RGCE – TEP – Specific Energy Consumption Slide 13 of 53

Specific Energy Consumption

EXEMPLO – Fabrica de Vidro

Como optimizar o Consumo especifico da fábrica?

Page 14: Energy Management :: 2007/2008 - Técnico Lisboa ... · Energy Management Class # 3P :: RGCE – TEP – Specific Energy Consumption Slide 8 of 53 Specific Energy Consumption EXEMPLO

Energy Management

Class # 3P :: RGCE – TEP – Specific Energy Consumption Slide 14 of 53

Course Organization

Week Dates Summary Assignement

1 10, 14  Set Sustainability and resource management

2 17, 21  Set Energy Markets OUT, 1

3 24, 28  Set Energy and environment: LCA Presentation TERM PAPER Topics

4 1, 5  Out Energy and environment: LCA OUT, 2 

5 8, 12 Out Energy Services Definition Term Paper Topics

6 15, 19  Out Energy Systems modeling: Blocks OUT, 3

7 22, 26  Out Energy Systems modeling: I‐O OUT, 4

8 29 Out, 2 Nov Energy Management in Industry

9 5, 9  Nov Main Energy Transformation Equipments Characterization, energy audits OUT, 5

10 12, 16 Nov Energy Management Systems in Industry

11 19, 23  Nov Integration of Energy Systems: Demand side management. OUT, 6

12 26, 30  Nov Energy Efficiency, tools and practice

13 3, 7  Dez Energy efficiency in buildings

14 10, 14  Dez The role of renewables

Page 15: Energy Management :: 2007/2008 - Técnico Lisboa ... · Energy Management Class # 3P :: RGCE – TEP – Specific Energy Consumption Slide 8 of 53 Specific Energy Consumption EXEMPLO

Energy Management

Class # 3P :: RGCE – TEP – Specific Energy Consumption Slide 15 of 53

Energy Management :: 2007/2008

Class # 3P

RGCE – TEP – Specific Energy Consumption

Dr. João [email protected]