Chapter 3Harmonic Modeling of Networks

Chapter 3Harmonic Modeling of Networks

Contributors: T. Ortmyer, C. Hatziadoniu, and P. Ribeiro

Tutorial on Harmonics Modeling and Simulation

Page 2: IEEE PES General Meeting, Tampa FL June 24-28, 2007 Conferência Brasileira de Qualidade de Energia Santos, São Paulo, Agosto 5-8, 2007 1 Chapter 3 Harmonic.

IEEE PES General Meeting, Tampa FLJune 24-28, 2007

Conferência Brasileira de Qualidade de EnergiaSantos, São Paulo, Agosto 5-8, 2007

2

Distribution System Modeling Distribution System Modeling

The initial decisions:

- Three phase or single phase modeling

- The extent of the primary model

- Secondary distribution modeling

The NATURE of the issue and the GOAL of thestudy constrain these decisions.

Page 3: IEEE PES General Meeting, Tampa FL June 24-28, 2007 Conferência Brasileira de Qualidade de Energia Santos, São Paulo, Agosto 5-8, 2007 1 Chapter 3 Harmonic.

IEEE PES General Meeting, Tampa FLJune 24-28, 2007

Conferência Brasileira de Qualidade de EnergiaSantos, São Paulo, Agosto 5-8, 2007

3

A Typical Primary Distribution SystemA Typical Primary Distribution System

Page 4: IEEE PES General Meeting, Tampa FL June 24-28, 2007 Conferência Brasileira de Qualidade de Energia Santos, São Paulo, Agosto 5-8, 2007 1 Chapter 3 Harmonic.

IEEE PES General Meeting, Tampa FLJune 24-28, 2007

Conferência Brasileira de Qualidade de EnergiaSantos, São Paulo, Agosto 5-8, 2007

4

Things to noteThings to note

• Any large or unique loads

• Capacitor banks/ cables(?)

• Transmission supply

• Any unusual operating conditions?

Page 5: IEEE PES General Meeting, Tampa FL June 24-28, 2007 Conferência Brasileira de Qualidade de Energia Santos, São Paulo, Agosto 5-8, 2007 1 Chapter 3 Harmonic.

IEEE PES General Meeting, Tampa FLJune 24-28, 2007

Conferência Brasileira de Qualidade de EnergiaSantos, São Paulo, Agosto 5-8, 2007

5

Decision 1: Per phase versus Three Phase Modeling

Decision 1: Per phase versus Three Phase Modeling

The three phase model is required when: Single phase or unbalanced capacitors are present Ground or residual currents are important in the study

Significant unbalanced loading is present A combination of wye-wye and/or delta-wye transformers leads to harmonic cancellation*

Page 6: IEEE PES General Meeting, Tampa FL June 24-28, 2007 Conferência Brasileira de Qualidade de Energia Santos, São Paulo, Agosto 5-8, 2007 1 Chapter 3 Harmonic.

IEEE PES General Meeting, Tampa FLJune 24-28, 2007

Conferência Brasileira de Qualidade de EnergiaSantos, São Paulo, Agosto 5-8, 2007

6

The typical instances where a single phase model may be sufficient are:

The typical instances where a single phase model may be sufficient are:

A single large three phase harmonic source is the cause of the study

The remaining system is well balanced

Ground currents are not an issue

Page 7: IEEE PES General Meeting, Tampa FL June 24-28, 2007 Conferência Brasileira de Qualidade de Energia Santos, São Paulo, Agosto 5-8, 2007 1 Chapter 3 Harmonic.

IEEE PES General Meeting, Tampa FLJune 24-28, 2007

Conferência Brasileira de Qualidade de EnergiaSantos, São Paulo, Agosto 5-8, 2007

7

Decision 2: The extent of the system model

Decision 2: The extent of the system model

Model the entire primary system

Transmission source can be modeled by the 60 Hertz short circuit impedance if no significant transmission capacitance is nearby– but check that the transmission system is not a source of harmonics

Power factor capacitors and any distributed generation should be modeled in detail

Page 8: IEEE PES General Meeting, Tampa FL June 24-28, 2007 Conferência Brasileira de Qualidade de Energia Santos, São Paulo, Agosto 5-8, 2007 1 Chapter 3 Harmonic.

IEEE PES General Meeting, Tampa FLJune 24-28, 2007

Conferência Brasileira de Qualidade de EnergiaSantos, São Paulo, Agosto 5-8, 2007

8

Decision 3: Load and harmonic source modeling

Decision 3: Load and harmonic source modeling

Identify and model all significant harmonic sources

Determine present levels through measurements- also determine if harmonic levels peak at full or light load conditions

Develop aggregate load models based on measurements and load distribution

Validate with measurements taken as harmonic sources/capacitor banks are switched in and out

Page 9: IEEE PES General Meeting, Tampa FL June 24-28, 2007 Conferência Brasileira de Qualidade de Energia Santos, São Paulo, Agosto 5-8, 2007 1 Chapter 3 Harmonic.

IEEE PES General Meeting, Tampa FLJune 24-28, 2007

Conferência Brasileira de Qualidade de EnergiaSantos, São Paulo, Agosto 5-8, 2007

9

Representative secondary distribution systemRepresentative secondary distribution system

Page 10: IEEE PES General Meeting, Tampa FL June 24-28, 2007 Conferência Brasileira de Qualidade de Energia Santos, São Paulo, Agosto 5-8, 2007 1 Chapter 3 Harmonic.

IEEE PES General Meeting, Tampa FLJune 24-28, 2007

Conferência Brasileira de Qualidade de EnergiaSantos, São Paulo, Agosto 5-8, 2007

10

Characteristics of secondary studiesCharacteristics of secondary studies

Different voltage levels

Fewer capacitors, and more with tuning coils

Load data is more accessible- and more important

Measurements can be more economical

Page 11: IEEE PES General Meeting, Tampa FL June 24-28, 2007 Conferência Brasileira de Qualidade de Energia Santos, São Paulo, Agosto 5-8, 2007 1 Chapter 3 Harmonic.

IEEE PES General Meeting, Tampa FLJune 24-28, 2007

Conferência Brasileira de Qualidade de EnergiaSantos, São Paulo, Agosto 5-8, 2007

11

Modeling transformersModeling transformers

• Model the transformer connection

• Neglect the transformer magnetizing branch (usually ignore the transformer magnetizing harmonics)

• Model the harmonic reactance as the product of short circuit leakage reactance and harmonic number

• Model the harmonic resistance as the short circuit resistance. Correct for skin effect if data or model available.

• Include stray capacitance for frequencies above the low khertz range.

Page 12: IEEE PES General Meeting, Tampa FL June 24-28, 2007 Conferência Brasileira de Qualidade de Energia Santos, São Paulo, Agosto 5-8, 2007 1 Chapter 3 Harmonic.

IEEE PES General Meeting, Tampa FLJune 24-28, 2007

Conferência Brasileira de Qualidade de EnergiaSantos, São Paulo, Agosto 5-8, 2007

12

Line ModelsLine Models

• Distribution lines and cables should be represented by an equivalent pi. An estimated correction factor for skin effect can be included

• Model ground path for zero sequence harmonics

Page 13: IEEE PES General Meeting, Tampa FL June 24-28, 2007 Conferência Brasileira de Qualidade de Energia Santos, São Paulo, Agosto 5-8, 2007 1 Chapter 3 Harmonic.

IEEE PES General Meeting, Tampa FLJune 24-28, 2007

Conferência Brasileira de Qualidade de EnergiaSantos, São Paulo, Agosto 5-8, 2007

13

CapacitorsCapacitors

• Capacitors– model as capacitive reactance– 60 hertz reactance divided by the harmonic number.

• Be sure to note those single phase capacitors, and model as such.

• Model the capacitor as either grounded wye, or ungrounded wye or delta.

Page 14: IEEE PES General Meeting, Tampa FL June 24-28, 2007 Conferência Brasileira de Qualidade de Energia Santos, São Paulo, Agosto 5-8, 2007 1 Chapter 3 Harmonic.

IEEE PES General Meeting, Tampa FLJune 24-28, 2007

Conferência Brasileira de Qualidade de EnergiaSantos, São Paulo, Agosto 5-8, 2007

14

Load ModelsLoad Models

• Linear Loads

• Induction and Synchronous Machines

• Non-linear Loads

Page 15: IEEE PES General Meeting, Tampa FL June 24-28, 2007 Conferência Brasileira de Qualidade de Energia Santos, São Paulo, Agosto 5-8, 2007 1 Chapter 3 Harmonic.

IEEE PES General Meeting, Tampa FLJune 24-28, 2007

Conferência Brasileira de Qualidade de EnergiaSantos, São Paulo, Agosto 5-8, 2007

15

Linear Passive LoadsLinear Passive Loads

• TYPES: Incandescent lamps, resistive heater, electric range, water heater, space heater, etc.

• CHARACTERISTICS: RL type loads with RL values independent of frequency.

R

jwhL=jhXL

Per Phase Model

Page 16: IEEE PES General Meeting, Tampa FL June 24-28, 2007 Conferência Brasileira de Qualidade de Energia Santos, São Paulo, Agosto 5-8, 2007 1 Chapter 3 Harmonic.

IEEE PES General Meeting, Tampa FLJune 24-28, 2007

Conferência Brasileira de Qualidade de EnergiaSantos, São Paulo, Agosto 5-8, 2007

16

Line Connected MOTOR/GENERATOR LOADS

Line Connected MOTOR/GENERATOR LOADS

Induction Motor Fundamental Frequency Per Phase Equivalent Circuit

synch

rotorsynch

n

nns

Page 17: IEEE PES General Meeting, Tampa FL June 24-28, 2007 Conferência Brasileira de Qualidade de Energia Santos, São Paulo, Agosto 5-8, 2007 1 Chapter 3 Harmonic.

IEEE PES General Meeting, Tampa FLJune 24-28, 2007

Conferência Brasileira de Qualidade de EnergiaSantos, São Paulo, Agosto 5-8, 2007

17

IM Per Phase Harmonic ModelIM Per Phase Harmonic Model

0.1

synch

rotorsynchh hn

nhns

Page 18: IEEE PES General Meeting, Tampa FL June 24-28, 2007 Conferência Brasileira de Qualidade de Energia Santos, São Paulo, Agosto 5-8, 2007 1 Chapter 3 Harmonic.

IEEE PES General Meeting, Tampa FLJune 24-28, 2007

Conferência Brasileira de Qualidade de EnergiaSantos, São Paulo, Agosto 5-8, 2007

18

• For synchronous generators, the per phase model of the synchronous generator is similar– use a series combination of stator resistance and substransient reactance in the model.

• On all direct connected machines, make sure and account for the ground connection (or lack of one) in studies with zero sequence harmonics.

Page 19: IEEE PES General Meeting, Tampa FL June 24-28, 2007 Conferência Brasileira de Qualidade de Energia Santos, São Paulo, Agosto 5-8, 2007 1 Chapter 3 Harmonic.

IEEE PES General Meeting, Tampa FLJune 24-28, 2007

Conferência Brasileira de Qualidade de EnergiaSantos, São Paulo, Agosto 5-8, 2007

19

Nonlinear LoadsNonlinear Loads

• Adjustable speed drives

• fluorescent lamps, computers and other electronic loads

• arc furnaces and welders

• These loads generate harmonic currents, and are modeled as sources at the harmonic frequencies

Page 20: IEEE PES General Meeting, Tampa FL June 24-28, 2007 Conferência Brasileira de Qualidade de Energia Santos, São Paulo, Agosto 5-8, 2007 1 Chapter 3 Harmonic.

IEEE PES General Meeting, Tampa FLJune 24-28, 2007

Conferência Brasileira de Qualidade de EnergiaSantos, São Paulo, Agosto 5-8, 2007

20

Load Model 1: Series Passive LoadLoad Model 1: Series Passive Load

2

2 2

2

2 2

VR P

P Q

VX Q

P Q

Page 21: IEEE PES General Meeting, Tampa FL June 24-28, 2007 Conferência Brasileira de Qualidade de Energia Santos, São Paulo, Agosto 5-8, 2007 1 Chapter 3 Harmonic.

IEEE PES General Meeting, Tampa FLJune 24-28, 2007

Conferência Brasileira de Qualidade de EnergiaSantos, São Paulo, Agosto 5-8, 2007

21

Load Model 2: Parallel Passive LoadLoad Model 2: Parallel Passive Load

2

2

VR

P

VX

Q

Page 22: IEEE PES General Meeting, Tampa FL June 24-28, 2007 Conferência Brasileira de Qualidade de Energia Santos, São Paulo, Agosto 5-8, 2007 1 Chapter 3 Harmonic.

IEEE PES General Meeting, Tampa FLJune 24-28, 2007

Conferência Brasileira de Qualidade de EnergiaSantos, São Paulo, Agosto 5-8, 2007

22

Load Model 3. Skin Effect Parallel Load Model

Load Model 3. Skin Effect Parallel Load Model

2

2

( )( )

( )( )

( ) 0.1 0.9

VR h

m h P

VX h

m h Q

m h h

Page 23: IEEE PES General Meeting, Tampa FL June 24-28, 2007 Conferência Brasileira de Qualidade de Energia Santos, São Paulo, Agosto 5-8, 2007 1 Chapter 3 Harmonic.

IEEE PES General Meeting, Tampa FLJune 24-28, 2007

Conferência Brasileira de Qualidade de EnergiaSantos, São Paulo, Agosto 5-8, 2007

23

Load Model 4. Induction Motor plus Resistive

Load Model 4. Induction Motor plus Resistive

2

1

2

11

1

(1 )

Install Factor ( 1.2)

Severity Factor ( 8)

fraction of motor load

m

m

VR

K P

VX

K K K P

K

K

K

Page 24: IEEE PES General Meeting, Tampa FL June 24-28, 2007 Conferência Brasileira de Qualidade de Energia Santos, São Paulo, Agosto 5-8, 2007 1 Chapter 3 Harmonic.

IEEE PES General Meeting, Tampa FLJune 24-28, 2007

Conferência Brasileira de Qualidade de EnergiaSantos, São Paulo, Agosto 5-8, 2007

24

Load Model 5. CIGRE/EDFLoad Model 5. CIGRE/EDF

2

2

2 22

1

(1 )

0.073

(6.7 tan 0.74)

tan

fraction of motor load

VR

K P

X R

VX

K P

QP

K

Page 25: IEEE PES General Meeting, Tampa FL June 24-28, 2007 Conferência Brasileira de Qualidade de Energia Santos, São Paulo, Agosto 5-8, 2007 1 Chapter 3 Harmonic.

IEEE PES General Meeting, Tampa FLJune 24-28, 2007

Conferência Brasileira de Qualidade de EnergiaSantos, São Paulo, Agosto 5-8, 2007

25

Load Model 6. Inclusion of Load Transformer and Motor DampingLoad Model 6. Inclusion of Load Transformer and Motor Damping

1 1

2 2

11

3

3

X and as in Model 4

X 0.1

is the effective quality factor

of the motor circuit.

R

R

XR K

K

Page 26: IEEE PES General Meeting, Tampa FL June 24-28, 2007 Conferência Brasileira de Qualidade de Energia Santos, São Paulo, Agosto 5-8, 2007 1 Chapter 3 Harmonic.

IEEE PES General Meeting, Tampa FLJune 24-28, 2007

Conferência Brasileira de Qualidade de EnergiaSantos, São Paulo, Agosto 5-8, 2007

26

I. Case Study 1: Load Impedance Frequency Study

I. Case Study 1: Load Impedance Frequency Study

0.001

0.0107H

11 kVSystemSource

HarmonicSource

Load

PFC

Page 27: IEEE PES General Meeting, Tampa FL June 24-28, 2007 Conferência Brasileira de Qualidade de Energia Santos, São Paulo, Agosto 5-8, 2007 1 Chapter 3 Harmonic.

IEEE PES General Meeting, Tampa FLJune 24-28, 2007

Conferência Brasileira de Qualidade de EnergiaSantos, São Paulo, Agosto 5-8, 2007

27

Case Study 1 ParametersCase Study 1 Parameters

• Linear Load=743 kW.

• PF Cap.=741kVAr, (C=5.4F).

• Injected Harmonic Currents (A):

• I5 = 0.840 I7 = 0.601

• I11=0.382 I13=0.323

Page 28: IEEE PES General Meeting, Tampa FL June 24-28, 2007 Conferência Brasileira de Qualidade de Energia Santos, São Paulo, Agosto 5-8, 2007 1 Chapter 3 Harmonic.

IEEE PES General Meeting, Tampa FLJune 24-28, 2007

Conferência Brasileira de Qualidade de EnergiaSantos, São Paulo, Agosto 5-8, 2007

28

Case Study 1: Load Model 1, 2, and 3 results

Case Study 1: Load Model 1, 2, and 3 results

Page 29: IEEE PES General Meeting, Tampa FL June 24-28, 2007 Conferência Brasileira de Qualidade de Energia Santos, São Paulo, Agosto 5-8, 2007 1 Chapter 3 Harmonic.

IEEE PES General Meeting, Tampa FLJune 24-28, 2007

Conferência Brasileira de Qualidade de EnergiaSantos, São Paulo, Agosto 5-8, 2007

29

Case Study 1: Load Model 4, 5, and 6 Results

Case Study 1: Load Model 4, 5, and 6 Results

Page 30: IEEE PES General Meeting, Tampa FL June 24-28, 2007 Conferência Brasileira de Qualidade de Energia Santos, São Paulo, Agosto 5-8, 2007 1 Chapter 3 Harmonic.

IEEE PES General Meeting, Tampa FLJune 24-28, 2007

Conferência Brasileira de Qualidade de EnergiaSantos, São Paulo, Agosto 5-8, 2007

30

Sensitivity of Impedance to Motor Penetration Level (Load Model 6, fixed PFC)

Sensitivity of Impedance to Motor Penetration Level (Load Model 6, fixed PFC)

Page 31: IEEE PES General Meeting, Tampa FL June 24-28, 2007 Conferência Brasileira de Qualidade de Energia Santos, São Paulo, Agosto 5-8, 2007 1 Chapter 3 Harmonic.

IEEE PES General Meeting, Tampa FLJune 24-28, 2007

Conferência Brasileira de Qualidade de EnergiaSantos, São Paulo, Agosto 5-8, 2007

31

Sensitivity of Impedance to IM Penetration– w/changing PFCSensitivity of Impedance to IM Penetration– w/changing PFC

Page 32: IEEE PES General Meeting, Tampa FL June 24-28, 2007 Conferência Brasileira de Qualidade de Energia Santos, São Paulo, Agosto 5-8, 2007 1 Chapter 3 Harmonic.

IEEE PES General Meeting, Tampa FLJune 24-28, 2007

Conferência Brasileira de Qualidade de EnergiaSantos, São Paulo, Agosto 5-8, 2007

32

SummarySummary

• Define study needs

• Determine the modeling needs

• Get the data

• Validate the data

• Produce good results!!