NBR 5410 2004 Corrigida 2008

download NBR 5410 2004 Corrigida 2008

of 217

Transcript of NBR 5410 2004 Corrigida 2008

  • 8/8/2019 NBR 5410 2004 Corrigida 2008

    1/217

    ABNT 2004

    Instalaes eltricas de baixa tenso

    Electrical installations of buildings Low voltage

    Palavra-chave: Instalao eltrica em edificao.Descriptor: Electrical installation of building.

    ICS 91.140.50

    ISBN 978-85-07-00562-9

    Nmero de refernciaABNT NBR 5410:2004209 pginas

    NORMABRASILEIRA

    ABNT NBR5410

    Segunda edio30.09.2004

    Vlida a partir de31.03.2005

    Verso Corrigida17.03.2008

  • 8/8/2019 NBR 5410 2004 Corrigida 2008

    2/217

    ABNT NBR 5410:2004

    ii ABNT 2004 Todos os direitos reservados

    ABNT 2004Todos os direitos reservados. A menos que especificado de outro modo, nenhuma parte desta publicao pode serreproduzida ou utilizada em qualquer forma ou por qualquer meio, eletrnico ou mecnico, incluindo fotocpia emicrofilme, sem permisso por escrito pela ABNT.

    Sede da ABNTAv. Treze de Maio, 13 28 andar20003-900 Rio de Janeiro RJTel.: + 55 21 3974-2300Fax: + 55 21 [email protected]

    www.abnt.org.brImpresso no Brasil

  • 8/8/2019 NBR 5410 2004 Corrigida 2008

    3/217

    ABNT NBR 5410:2004

    ABNT 2004 Todos os direitos reservados iii

    Sumrio Pgina

    Prefcio.............................................................................................................................................................. vii

    1 Objetivo .................................................................................................................................................. 1

    2 Referncias normativas ........................................................................................................................ 2

    3 Definies .............................................................................................................................................. 73.1 Componentes da instalao ................................................................................................................. 73.2 Proteo contra choques eltricos ..................................................................................................... 73.3 Proteo contra choques eltricos e proteo contra sobretenses e perturbaes

    eletromagnticas ................................................................................................................................... 73.4 Linhas eltricas ..................................................................................................................................... 83.5 Servios de segurana ......................................................................................................................... 9

    4 Princpios fundamentais e determinao das caractersticas gerais ............................................ 104.1 Princpios fundamentais ..................................................................................................................... 104.1.1 Proteo contra choques eltricos ................................................................................................... 104.1.2 Proteo contra efeitos trmicos ...................................................................................................... 104.1.3 Proteo contra sobrecorrentes ........................................................................................................ 104.1.4 Circulao de correntes de falta ........................................................................................................ 104.1.5 Proteo contra sobretenses ........................................................................................................... 104.1.6 Servios de segurana ....................................................................................................................... 104.1.7 Desligamento de emergncia ............................................................................................................. 11

    4.1.8 Seccionamento .................................................................................................................................... 114.1.9 Independncia da instalao eltrica ................................................................................................ 114.1.10 Acessibilidade dos componentes ..................................................................................................... 114.1.11 Seleo dos componentes ................................................................................................................. 114.1.12 Preveno de efeitos danosos ou indesejados ............................................................................... 114.1.13 Instalao dos componentes ............................................................................................................. 114.1.14 Verificao da instalao ................................................................................................................... 124.1.15 Qualificao profissional .................................................................................................................... 124.2 Determinao das caractersticas gerais ......................................................................................... 124.2.1 Utilizao e demanda Potncia de alimentao ............................................................................ 124.2.2 Esquema de distribuio .................................................................................................................... 134.2.3 Alimentaes ....................................................................................................................................... 174.2.4 Servios de segurana ....................................................................................................................... 18

    4.2.5 Diviso da instalao .......................................................................................................................... 184.2.6 Classificao das influncias externas............................................................................................. 194.2.7 Compatibilidade ................................................................................................................................... 344.2.8 Manuteno .......................................................................................................................................... 34

    5 Proteo para garantir segurana ..................................................................................................... 355.1 Proteo contra choques eltricos ................................................................................................... 355.1.1 Introduo ............................................................................................................................................ 355.1.2 Medidas de proteo ........................................................................................................................... 365.1.3 Proteo adicional ............................................................................................................................... 485.1.4 Aplicao das medidas de proteo contra choques eltricos ..................................................... 505.1.5 Proteo parcial contra choques eltricos ....................................................................................... 515.1.6 Omisso da proteo contra choques eltricos .............................................................................. 535.2 Proteo contra efeitos trmicos ...................................................................................................... 56

    5.2.1 Generalidades ...................................................................................................................................... 565.2.2 Proteo contra incndio ................................................................................................................... 565.2.3 Proteo contra queimaduras ............................................................................................................ 60

  • 8/8/2019 NBR 5410 2004 Corrigida 2008

    4/217

    ABNT NBR 5410:2004

    iv ABNT 2004 Todos os direitos reservados

    5.3 Proteo contra sobrecorrentes ........................................................................................................615.3.1 Generalidades ......................................................................................................................................615.3.2 Proteo de acordo com a natureza dos circuitos ..........................................................................615.3.3 Natureza dos dispositivos de proteo .............................................................................................625.3.4 Proteo contra correntes de sobrecarga ........................................................................................63

    5.3.5 Proteo contra correntes de curto-circuito ....................................................................................655.3.6 Coordenao entre a proteo contra sobrecargas e a proteo contra curtos-circuitos .........685.3.7 Limitao das sobrecorrentes atravs das caractersticas da alimentao .................................685.4 Proteo contra sobretenses e perturbaes eletromagnticas .................................................695.4.1 Proteo contra sobretenses temporrias .....................................................................................695.4.2 Proteo contra sobretenses transitrias ......................................................................................695.4.3 Preveno de influncias eletromagnticas nas instalaes e seus componentes ....................715.5 Proteo contra quedas e faltas de tenso ......................................................................................735.6 Seccionamento e comando ................................................................................................................735.6.1 Introduo ............................................................................................................................................735.6.2 Generalidades ......................................................................................................................................735.6.3 Seccionamento ....................................................................................................................................735.6.4 Seccionamento para manuteno mecnica ....................................................................................74

    5.6.5 Seccionamento de emergncia e parada de emergncia ................................................................755.6.6 Comando funcional .............................................................................................................................75

    6 Seleo e instalao dos componentes ............................................................................................766.1 Prescries comuns a todos os componentes da instalao ........................................................766.1.1 Generalidades ......................................................................................................................................766.1.2 Conformidade com as normas ...........................................................................................................766.1.3 Condies de servio e influncias externas ...................................................................................776.1.4 Acessibilidade ......................................................................................................................................866.1.5 Identificao dos componentes .........................................................................................................866.1.6 Independncia dos componentes ......................................................................................................876.1.7 Compatibilidade eletromagntica ......................................................................................................876.1.8 Documentao da instalao .............................................................................................................87

    6.2 Seleo e instalao das linhas eltricas .........................................................................................886.2.1 Generalidades ......................................................................................................................................886.2.2 Tipos de linhas eltricas .....................................................................................................................886.2.3 Condutores ...........................................................................................................................................886.2.4 Seleo e instalao em funo das influncias externas .............................................................956.2.5 Capacidades de conduo de corrente .............................................................................................986.2.6 Condutores de fase e condutor neutro .......................................................................................... 1136.2.7 Quedas de tenso ............................................................................................................................. 1156.2.8 Conexes ........................................................................................................................................... 1166.2.9 Condies gerais de instalao ...................................................................................................... 1176.2.10 Disposio dos condutores ............................................................................................................. 1196.2.11 Prescries para instalao ............................................................................................................ 1206.3 Dispositivos de proteo, seccionamento e comando ................................................................. 125

    6.3.1 Generalidades ................................................................................................................................... 1256.3.2 Prescries comuns ......................................................................................................................... 1256.3.3 Dispositivos destinados a assegurar o seccionamento automtico da alimentao

    visando proteo contra choques eltricos .................................................................................. 1256.3.4 Dispositivos de proteo contra sobrecorrentes .......................................................................... 1276.3.5 Dispositivos de proteo contra surtos (DPS) .............................................................................. 1306.3.6 Coordenao entre diferentes dispositivos de proteo ............................................................. 1386.3.7 Dispositivos de seccionamento e de comando ............................................................................. 1386.4 Aterramento e eqipotencializao ................................................................................................ 1426.4.1 Aterramento ....................................................................................................................................... 1426.4.2 Eqipotencializao ......................................................................................................................... 1456.4.3 Condutores de proteo (PE) .......................................................................................................... 1476.4.4 Condutores de eqipotencializao ............................................................................................... 152

    6.4.5 Eqipotencializao funcional ........................................................................................................ 1526.4.6 Aterramento por razes funcionais ................................................................................................ 1536.4.7 Aterramento combinado (funcional e de proteo) ...................................................................... 153

  • 8/8/2019 NBR 5410 2004 Corrigida 2008

    5/217

    ABNT NBR 5410:2004

    ABNT 2004 Todos os direitos reservados v

    6.5 Outros componentes ........................................................................................................................ 1546.5.1 Motores eltricos ............................................................................................................................... 1546.5.2 Bateria de acumuladores .................................................................................................................. 1566.5.3 Tomadas de corrente e extenses .................................................................................................. 1566.5.4 Conjuntos de proteo, manobra e comando ................................................................................ 157

    6.5.5 Equipamentos de utilizao ............................................................................................................. 1586.6 Servios de segurana ..................................................................................................................... 1606.6.6 Fontes de segurana ......................................................................................................................... 1616.6.7 Circuitos de segurana ..................................................................................................................... 1626.6.8 Equipamentos de utilizao ............................................................................................................. 163

    7 Verificao final ................................................................................................................................. 1637.1 Prescries gerais ............................................................................................................................. 1637.2 Inspeo visual .................................................................................................................................. 1637.3 Ensaios ............................................................................................................................................... 1647.3.1 Prescries gerais ............................................................................................................................. 1647.3.2 Continuidade dos condutores de proteo, incluindo as eqipotencializaes principal e

    suplementares ................................................................................................................................... 1647.3.3 Resistncia de isolamento da instalao ....................................................................................... 1657.3.4 Resistncia de isolamento aplicvel a SELV, PELV e separao eltrica .................................. 1657.3.5 Verificao das condies de proteo por eqipotencializao e seccionamento

    automtico da alimentao .............................................................................................................. 1657.3.6 Ensaio de tenso aplicada ............................................................................................................... 1677.3.7 Ensaios de funcionamento ............................................................................................................... 168

    8 Manuteno ........................................................................................................................................ 1688.1 Periodicidade ..................................................................................................................................... 1688.2 Qualificao do pessoal ................................................................................................................... 1688.3 Verificaes de rotina Manuteno preventiva ........................................................................... 1688.3.1 Condutores ........................................................................................................................................ 1688.3.2 Quadros de distribuio e painis ................................................................................................... 1698.3.3 Equipamentos mveis ...................................................................................................................... 169

    8.3.4 Ensaios ............................................................................................................................................... 1698.3.5 Ensaio geral ....................................................................................................................................... 1698.4 Manuteno corretiva ....................................................................................................................... 169

    9 Requisitos complementares para instalaes ou locais especficos .......................................... 1709.1 Locais contendo banheira ou chuveiro .......................................................................................... 1709.1.1 Campo de aplicao .......................................................................................................................... 1709.1.2 Determinao das caractersticas gerais ....................................................................................... 1709.1.3 Proteo para garantir segurana ................................................................................................... 1739.1.4 Seleo e instalao dos componentes ......................................................................................... 1739.2 Piscinas .............................................................................................................................................. 1759.2.1 Campo de aplicao .......................................................................................................................... 1759.2.2 Determinao das caractersticas gerais ....................................................................................... 175

    9.2.3 Proteo para garantir segurana ................................................................................................... 1769.2.4 Seleo e instalao dos componentes ......................................................................................... 1779.3 Compartimentos condutivos ............................................................................................................ 1799.3.1 Campo de aplicao .......................................................................................................................... 1799.3.2 Alimentao de ferramentas portteis e de aparelhos de medio portteis ............................ 1799.3.3 Alimentao de lmpadas portteis ................................................................................................ 1809.3.4 Alimentao dos equipamentos fixos ............................................................................................. 1809.3.5 SELV ................................................................................................................................................... 1809.3.6 Separao eltrica individual ........................................................................................................... 1809.4 Locais contendo aquecedores de sauna ........................................................................................ 1809.4.1 Campo de aplicao .......................................................................................................................... 1809.4.2 Classificao dos volumes .............................................................................................................. 1809.4.3 Proteo para garantir segurana ................................................................................................... 181

    9.4.4 Seleo e instalao dos componentes ......................................................................................... 1819.5 Locais de habitao .......................................................................................................................... 1829.5.1 Campo de aplicao .......................................................................................................................... 182

  • 8/8/2019 NBR 5410 2004 Corrigida 2008

    6/217

    ABNT NBR 5410:2004

    vi ABNT 2004 Todos os direitos reservados

    9.5.2 Previso de carga ............................................................................................................................. 1829.5.3 Diviso da instalao ....................................................................................................................... 1849.5.4 Proteo contra sobrecorrentes ..................................................................................................... 184

    Anexo A (normativo) Faixas de tenso ........................................................................................................ 185

    Anexo B (normativo) Meios de proteo bsica (contra choques eltricos) ........................................... 186B.1 Isolao (bsica) das partes vivas .................................................................................................. 186B.2 Uso de barreiras ou invlucros ....................................................................................................... 186

    Anexo C (normativo) Influncias externas e proteo contra choques eltricos) .................................. 188C.1 Influncias externas determinantes................................................................................................ 188C.2 Situaes 1, 2 e 3 .............................................................................................................................. 188C.3 Tenso de contato limite .................................................................................................................. 189

    Anexo D (informativo) Proteo de condutores em paralelo contra sobrecorrentes .............................. 190D.1 Introduo ......................................................................................................................................... 190D.2 Proteo contra sobrecarga de condutores em paralelo ............................................................. 190D.3 Proteo contra curtos-circuitos de condutores em paralelo ..................................................... 192

    Anexo E (informativo) Categorias de suportabilidade a impulsos (categorias de sobretenses ou,ainda, nveis de proteo contra surtos) ....................................................................................... 195E.1 Introduo ......................................................................................................................................... 195E.2 As categorias .................................................................................................................................... 195

    Anexo F (informativo) Seo do condutor neutro quando o contedo de terceira harmnica dascorrentes de fase for superior a 33%.............................................................................................. 196

    F.1 Determinao da corrente de neutro .............................................................................................. 196F.2 Caso de condutores isolados ou cabos unipolares ..................................................................... 197F.3 Caso de cabos tetra e pentapolares ............................................................................................... 197

    Anexo G (informativo) Eqipotencializao principal ................................................................................ 198

    Anexo H (normativo) Verificao da atuao de dispositivos a corrente diferencial-residual(dispositivos DR) .............................................................................................................................. 200

    H.1.1 Mtodo 1 (ver figura H.1) .................................................................................................................. 200H.1.2 Mtodo 2 (ver figura H.2) .................................................................................................................. 200H.1.3 Mtodo 3 ............................................................................................................................................ 201

    Anexo J (normativo) Medio da resistncia de aterramento .................................................................... 202J.1.1 Mtodo 1 (ver figura J.1) .................................................................................................................. 202J.1.2 Mtodo 2 ............................................................................................................................................ 203

    Anexo K (normativo) Medio da impedncia do percurso da corrente de falta .................................... 204K.1 Mtodo 1 Medio da impedncia do percurso da corrente de falta por meio da queda

    de tenso (ver figura K.1) ................................................................................................................. 204K.2 Mtodo 2 Medio da impedncia do percurso da corrente de falta por meio de fonte

    separada (ver figura K.2) .................................................................................................................. 205

    Anexo L (normativo) Medio da resistncia dos condutores de proteo ............................................ 207Anexo M (normativo) Ensaio de tenso aplicada ........................................................................................ 209

  • 8/8/2019 NBR 5410 2004 Corrigida 2008

    7/217

    ABNT NBR 5410:2004

    ABNT 2004 Todos os direitos reservados vii

    Prefcio

    A Associao Brasileira de Normas Tcnicas (ABNT) o Frum Nacional de Normalizao. As Normas Brasileiras, cujo contedo de responsabilidade dos Comits Brasileiros (ABNT/CB), dosOrganismos de Normalizao Setorial (ABNT/ONS) e das Comisses de Estudo Especiais Temporrias(ABNT/CEET), so elaboradas por Comisses de Estudo (CE), formadas por representantes dos setoresenvolvidos, delas fazendo parte: produtores, consumidores e neutros (universidades, laboratrios e outros).

    A ABNT NBR 5410 foi elaborada no Comit Brasileiro de Eletricidade (ABNT/CB-03), pela Comisso deEstudo de Instalaes Eltricas de Baixa Tenso (CE03:064.01). O Projeto circulou em Consulta Pblicaconforme Edital n 09, de 30.09.2003, com o nmero Projeto NBR 5410.

    A partir de 31 de maro de 2005, esta Norma dever cancelar e substituir a edio anterior(ABNT NBR 5410:1997), a qual foi tecnicamente revisada.

    Esta Norma contm os anexos A, B, C, H, J, K, L e M, de carter normativo, e os anexos D, E, F e G, decarter informativo.

    Esta verso corrigida da ABNT NBR 5410:2004 incorpora a Errata 1 de 17.03.2008.

  • 8/8/2019 NBR 5410 2004 Corrigida 2008

    8/217

  • 8/8/2019 NBR 5410 2004 Corrigida 2008

    9/217

    NORMA BRASILEIRA ABNT NBR 5410:2004

    ABNT 2004 Todos os direitos reservados 1

    Instalaes eltricas de baixa tenso

    1 Objetivo

    1.1 Esta Norma estabelece as condies a que devem satisfazer as instalaes eltricas de baixa tenso,a fim de garantir a segurana de pessoas e animais, o funcionamento adequado da instalao e aconservao dos bens.

    1.2 Esta Norma aplica-se principalmente s instalaes eltricas de edificaes, qualquer que seja seu uso(residencial, comercial, pblico, industrial, de servios, agropecurio, hortigranjeiro, etc.), incluindo aspr-fabricadas.

    1.2.1 Esta Norma aplica-se tambm s instalaes eltricas:

    a) em reas descobertas das propriedades, externas s edificaes;

    b) de reboques de acampamento (trailers), locais de acampamento (campings), marinas e instalaesanlogas; e

    c) de canteiros de obra, feiras, exposies e outras instalaes temporrias.

    1.2.2 Esta Norma aplica-se:

    a) aos circuitos eltricos alimentados sob tenso nominal igual ou inferior a 1 000 V em corrente alternada,com freqncias inferiores a 400 Hz, ou a 1 500 V em corrente contnua;

    b) aos circuitos eltricos, que no os internos aos equipamentos, funcionando sob uma tenso superior a1 000 V e alimentados atravs de uma instalao de tenso igual ou inferior a 1 000 V em correntealternada (por exemplo, circuitos de lmpadas a descarga, precipitadores eletrostticos etc.);

    c) a toda fiao e a toda linha eltrica que no sejam cobertas pelas normas relativas aos equipamentos deutilizao; e

    d) s linhas eltricas fixas de sinal (com exceo dos circuitos internos dos equipamentos).

    NOTA A aplicao s linhas de sinal concentra-se na preveno dos riscos decorrentes das influncias mtuasentre essas linhas e as demais linhas eltricas da instalao, sobretudo sob os pontos de vista da segurana contrachoques eltricos, da segurana contra incndios e efeitos trmicos prejudiciais e da compatibilidade eletromagntica.

    1.2.3 Esta Norma aplica-se s instalaes novas e a reformas em instalaes existentes.

    NOTA Modificaes destinadas a, por exemplo, acomodar novos equipamentos eltricos, inclusive de sinal, ousubstituir equipamentos existentes, no caracterizam necessariamente uma reforma geral da instalao.

    1.3 Esta Norma no se aplica a:

    a) instalaes de trao eltrica;

    b) instalaes eltricas de veculos automotores;

    c) instalaes eltricas de embarcaes e aeronaves;

  • 8/8/2019 NBR 5410 2004 Corrigida 2008

    10/217

    ABNT NBR 5410:2004

    2 ABNT 2004 Todos os direitos reservados

    d) equipamentos para supresso de perturbaes radioeltricas, na medida que no comprometam asegurana das instalaes;

    e) instalaes de iluminao pblica;

    f) redes pblicas de distribuio de energia eltrica;

    g) instalaes de proteo contra quedas diretas de raios. No entanto, esta Norma considera asconseqncias dos fenmenos atmosfricos sobre as instalaes (por exemplo, seleo dos dispositivosde proteo contra sobretenses);

    h) instalaes em minas;

    i) instalaes de cercas eletrificadas (ver IEC 60335-2-76).

    1.4 Os componentes da instalao so considerados apenas no que concerne sua seleo e condiesde instalao. Isto igualmente vlido para conjuntos em conformidade com as normas a eles aplicveis.

    1.5 A aplicao desta Norma no dispensa o atendimento a outras normas complementares, aplicveis ainstalaes e locais especficos.

    NOTA So exemplos de normas complementares a esta Norma as ABNT NBR 13534, ABNT NBR 13570 eABNT NBR 5418.

    1.6 A aplicao desta Norma no dispensa o respeito aos regulamentos de rgos pblicos aos quais ainstalao deva satisfazer.

    1.7 As instalaes eltricas cobertas por esta Norma esto sujeitas tambm, naquilo que for pertinente, snormas para fornecimento de energia estabelecidas pelas autoridades reguladoras e pelas empresasdistribuidoras de eletricidade.

    2 Referncias normativas

    As normas relacionadas a seguir contm disposies que, ao serem citadas neste texto, constituemprescries para esta Norma. As edies indicadas estavam em vigor no momento desta publicao.Como toda norma est sujeita a reviso, recomenda-se queles que realizam acordos com base nesta queverifiquem a convenincia de se usarem as edies mais recentes das normas citadas a seguir.A ABNT possui a informao das normas em vigor em um dado momento.

    ABNT NBR 5361:1998 Disjuntores de baixa tenso

    ABNT NBR 5413:1992 Iluminncia de interiores Procedimento

    ABNT NBR 5418:1995 Instalaes eltricas em atmosferas explosivas

    ABNT NBR 5419:2001 Proteo de estruturas contra descargas atmosfricas

    ABNT NBR 5597:1995 Eletroduto rgido de ao-carbono e acessrios com revestimento protetor, com roscaANSI/ASME B1.20.1 Especificao

    ABNT NBR 5598:1993 Eletroduto rgido de ao-carbono com revestimento protetor, com roscaABNT NBR 6414 Especificao

    ABNT NBR 5624:1993 Eletroduto rgido de ao-carbono, com costura, com revestimento protetor e roscaABNT NBR 8133 Especificao

    ABNT NBR 6147:2000 Plugues e tomadas para uso domstico e anlogo Especificao

  • 8/8/2019 NBR 5410 2004 Corrigida 2008

    11/217

    ABNT NBR 5410:2004

    ABNT 2004 Todos os direitos reservados 3

    ABNT NBR 6150:1980 Eletrodutos de PVC rgido Especificao

    ABNT NBR 6524:1998 Fios e cabos de cobre duro e meio duro com ou sem cobertura protetora parainstalaes areas Especificao

    ABNT NBR 6527:2000 Interruptores para instalao eltrica fixa domstica e anloga Especificao

    ABNT NBR 6812:1995 Fios e cabos eltricos Queima vertical (fogueira) Mtodo de ensaio

    ABNT NBR 7094:2003 Mquinas eltricas girantes Motores de induo Especificao

    ABNT NBR 7285:2001 Cabos de potncia com isolao extrudada de polietileno termofixo (XLPE) paratenso de 0,6 kV/1 kV Sem cobertura Especificao

    ABNT NBR 7286:2001 Cabos de potncia com isolao extrudada de borracha etileno-propileno (EPR)para tenses de 1 kV a 35 kV Requisitos de desempenho

    ABNT NBR 7287:1992 Cabos de potncia com isolao slida extrudada de polietileno reticulado (XLPE)

    para tenses de isolamento de 1 kV a 35 kV Especificao

    ABNT NBR 7288:1994 Cabos de potncia com isolao slida extrudada de cloreto de polivinila (PVC) oupolietileno (PE) para tenses de 1 kV a 6 kV Especificao

    ABNT NBR 8661:1997 Cabos de formato plano com isolao extrudada de cloreto de polivinila (PVC) paratenso at 750 V Especificao

    ABNT NBR 9313:1986 Conectores para cabos de potncia isolados para tenses at 35 kV Condutoresde cobre ou alumnio Especificao

    ABNT NBR 9326:1986 Conectores para cabos de potncia Ensaios de ciclos trmicos e curto-circuito Mtodo de ensaio

    ABNT NBR 9513:1986 Emendas para cabos de potncia isolados para tenses at 750 V Especificao

    ABNT NBR 9518:1997 Equipamentos eltricos para atmosferas explosivas Requisitos gerais

    ABNT NBR 11301:1990 Clculo da capacidade de conduo de corrente de cabos isolados em regimepermanente (fator de carga 100%) Procedimento

    ABNT NBR 13248:2000 Cabos de potncia e controle e condutores isolados sem cobertura, com isolaoextrudada e com baixa emisso de fumaa para tenses at 1 kV Requisitos de desempenho

    ABNT NBR 13249:2000 Cabos e cordes flexveis para tenses at 750 V Especificao

    ABNT NBR 13300:1995 Redes telefnicas internas em prdios Terminologia

    ABNT NBR 13534:1995 Instalaes eltricas em estabelecimentos assistenciais de sade Requisitospara segurana

    ABNT NBR 13570:1996 Instalaes eltricas em locais de afluncia de pblico Requisitos especficos

    ABNT NBR 14136:2002 Plugues e tomadas para uso domstico e anlogo at 20 A/250 V em correntealternada Padronizao

    ABNT NBR 14306:1999 Proteo eltrica e compatibilidade eletromagntica em redes internas detelecomunicaes em edificaes Projeto

    ABNT NBR IEC 60050 (826):1997 Vocabulrio eletrotcnico internacional Captulo 826: Instalaeseltricas em edificaes

  • 8/8/2019 NBR 5410 2004 Corrigida 2008

    12/217

    ABNT NBR 5410:2004

    4 ABNT 2004 Todos os direitos reservados

    ABNT NBR IEC 60269-1:2003 Dispositivos fusveis de baixa tenso Parte 1: Requisitos gerais

    ABNT NBR IEC 60269-2:2003 Dispositivos fusveis de baixa tenso Parte 2: Requisitos adicionais paradispositivos fusveis para uso por pessoas autorizadas (dispositivos fusveis principalmente para aplicaoindustrial)

    ABNT NBR IEC 60269-3:2003 Dispositivos fusveis de baixa tenso Parte 3: Requisitos suplementarespara dispositivos fusveis para uso por pessoas no qualificadas (dispositivos fusveis principalmente paraaplicaes domsticas e similares)

    ABNT NBR IEC 60439-1:2003 Conjuntos de manobra e controle de baixa tenso Parte 1: Conjuntos comensaio de tipo totalmente testados (TTA) e conjuntos com ensaio de tipo parcialmente testados (PTTA)

    ABNT NBR IEC 60439-3:2004 Conjuntos de manobra e controle de baixa tenso Parte 3: Requisitosparticulares para montagem de acessrios de baixa tenso destinados a instalao em locais acessveis apessoas no qualificadas durante sua utilizao Quadros de distribuio

    ABNT NBR IEC 60947-2:1998 Dispositivos de manobra e comando de baixa tenso Parte 2: Disjuntores

    ABNT NBR NM 247-3:2002 Cabos isolados com policloreto de vinila (PVC) para tenses nominais at450/750 V, inclusive Parte 3: Condutores isolados (sem cobertura) para instalaes fixas(IEC 60227-3,MOD)

    ABNT NBR NM 60898:2004 Disjuntores para proteo de sobrecorrentes para instalaes domsticas esimilares (IEC 60898:1995, MOD)

    IEC 60038:2002 IEC standard voltages

    IEC 60079-0:2004 Electrical apparatus for explosive gas atmosphere Part 0: General requirements

    IEC 60079-14:2002 Electrical apparatus for explosive gas atmospheres Part 14: Electrical installations inhazardous areas (other than mines)

    IEC 60146-2:1999 Semiconductor converters Part 2: Self-commutated semiconductor converters includingdirect d.c. converters

    IEC 60255-22-1:1988 Electrical relays - Part 22: Electrical disturbance tests for measuring relays andprotection equipment Part 1: 1 MHz burst disturbance tests

    IEC 60309-1:1999 Plugs, socket-outlets and couplers for industrial purposes Part 1: General requirements

    IEC 60335-2-76:2002 Household and similar electrical appliances Safety Part 2-76: Particularrequirements for electric fence energizers

    IEC 60364-5-51:2001 Electrical installations of buildings Part 5-51: Selection and erection of electricalequipment Common rules

    IEC 60364-5-52:2001 Electrical installations of buildings Part 5-52: Selection and erection of electricalequipment Wiring systems

    IEC 60364-5-54:2002 Electrical installations of buildings Part 5-54: Selection and erection of electricalequipment Earthing arrangements, protective conductors and protective bonding conductors

    IEC 60439-2:2000 Low-voltage switchgear and controlgear assemblies Part 2: Particular requirements forbusbar trunking systems (busways)

    IEC 60439-4:2004 Low-voltage switchgear and controlgear assemblies Part 4: Particular requirements forassemblies for construction sites (ACS)

  • 8/8/2019 NBR 5410 2004 Corrigida 2008

    13/217

    ABNT NBR 5410:2004

    ABNT 2004 Todos os direitos reservados 5

    IEC 60439-5:1998 Low-voltage switchgear and controlgear assemblies Part 5: Particular requirements forassemblies intended to be installed outdoors in public places Cable distribution cabinets (CDCs) for powerdistribution in networks

    IEC 60529:2001 Degrees of protection provided by enclosures (IP Code)

    IEC 60598-2-18:1993 Luminaires Part 2: Particular requirements Section 18: Luminaires for swimmingpools and similar applications

    IEC 60598-2-22:2002 Luminaires Part 2-22: Particular requirements Luminaires for emergency lighting

    IEC 60614-1:1995 Conduits for electrical installations - Specification Part 1: General requirements

    IEC 60664-1:2002 Insulation coordination for equipment within low-voltage systems Part 1: Principles,requirements and tests

    IEC 60669-1:2000 Switches for household and similar fixed-electrical installations Part 1: Generalrequirements

    IEC 60721-3-3:2002 Classification of environmental conditions Part 3-3: Classification of groups ofenvironmental parameters and their severities Stationary use at weatherprotected locations

    IEC 60721-3-4:1995 Classification of environmental conditions Part 3-4: Classification of groups ofenvironmental parameters and their severities Stationary use at non-weatherprotected locations

    IEC 60724:2000 Short-circuit temperature limits of electric cables with rated voltages of 1 kV (Um = 1,2 kV)and 3 kV (Um = 3,6 kV)

    IEC 61000-2-1:1990 Electromagnetic compatibility (EMC) Part 2: Environment - Section 1 Description ofthe environment Electromagnetic environment for low-frequency conducted disturbances and signalling inpublic power supply systems

    IEC 61000-2-2:2002 Electromagnetic compatibility (EMC) Part 2-2: Environment Compatibility levels forlow frequency conducted disturbances and signalling in public low-voltage power supply systems

    IEC 61000-2-5:1995 Electromagnetic compatibility (EMC) Part 2: Environment Section 5: - Classificationof electromagnetic environments. Basic EMC publication

    IEC 61000-4-2:2001 Electromagnetic compatibility (EMC) Part 4-2: Testing and measurement techniques Electrostatic discharge immunity test

    IEC 61000-4-3:2002 Electromagnetic compatibility (EMC) Part 4-3: Testing and measurement techniques radiated, radio-frequency, electromagnetic field immunity test

    IEC 61000-4-4:2004 Electromagnetic compatibility (EMC) Part 4: Testing and measurement techniques Electrical fast transient/burst immunity test

    IEC 61000-4-6:2003 Electromagnetic compatibility (EMC) Part 4-6: Testing and measurement techniques Immunity to conducted disturbances, induced by radio-frequency fields

    IEC 61000-4-8:2001 Electromagnetic compatibility (EMC) Part 4-8: Testing and measurement techniques Power frequency magnetic field immunity test

    IEC 61000-4-12:2001 Electromagnetic compatibility (EMC) Part 4-12: Testing and measurementtechniques Oscillatory waves immunity test

    IEC 61008-2-1:1990 Residual current operated circuit-breakers without integral overcurrent protection forhousehold and similar uses (RCCB's) Part 2-1: Applicability of the general rules to RCCB's functionallyindependent of line voltage

  • 8/8/2019 NBR 5410 2004 Corrigida 2008

    14/217

    ABNT NBR 5410:2004

    6 ABNT 2004 Todos os direitos reservados

    IEC 61009-2-1:1991 Residual current operated circuit-breakers with integral overcurrent protection forhousehold and similar uses (RCBO's) Part 2-1: Applicability of the general rules to RCBO's functionallyindependent of line voltage

    IEC 61084-1:1993 Cable trunking and ducting systems for electrical installations Part 1: General

    requirements

    IEC 61140:2001 Protection against electric shock Common aspects for installation and equipment

    IEC 60309-1:1999 Plugs, socket-outlets and couplers for industrial purposes Part 1: General requirements

    IEC 61312-1:1995 Protection against lightning electromagnetic impulse Part 1: General principles

    IEC 61386-1:2000 Conduit systems for electrical installations Part 1: General requirements

    IEC 61558-2-4:1997 Safety of power transformers, power supply units and similar Part 2: Particularrequirements for isolating transformers for general use

    IEC 61558-2-5:1997 Safety of power transformers, power supply units and similar Part 2-5: Particularrequirements for shaver transformers and shaver supply units

    IEC 61558-2-6:1997 Safety of power transformers, power supply units and similar Part 2: Particularrequirements for safety isolating transformers for general use

    IEC 61643-1:2002 Surge protective devices connected to low-voltage power distribution systems Part 1: Performance requirements and testing methods

    IEC 61663-2:2001 Lightning protection - Telecommunication lines Part 2: Lines using metallic conductors

    IEC/CISPR 11:2004 Industrial, scientific and medical (ISM) radio-frequency equipment Electromagneticdisturbance characteristics Limits and methods of measurement

    IEC/CISPR 12:2001 Vehicles, boats, and internal combustion engine driven devices Radio disturbancecharacteristics Limits and methods of measurement for the protection of receivers except those installed inthe vehicle/boat/device itself or in adjacent vehicles/boats/devices

    IEC/CISPR 13:2003 Sound and television broadcast receivers and associated equipment Radiodisturbance characteristics Limits and methods of measurement

    IEC/CISPR 14-1:2002 Electromagnetic compatibility Requirements for household appliances, electric toolsand similar apparatus Part 1 : Emission

    IEC/CISPR 14-2:2001 Electromagnetic compatibility Requirements for household appliances, electric tools

    and similar apparatus Part 2 : Immunity Product family standard

    IEC/CISPR 15:2002 Limits and methods of measurement of radio disturbance characteristic of electricallighting and similar equipment

    IEC/CISPR 22:2003 Information technology equipment Radio disturbance characteristics Limits andmethods of measurement

  • 8/8/2019 NBR 5410 2004 Corrigida 2008

    15/217

    ABNT NBR 5410:2004

    ABNT 2004 Todos os direitos reservados 7

    3 Definies

    Para os efeitos desta Norma, aplicam-se as definies da ABNT NBR IEC 60050(826) e as seguintes:

    3.1 Componentes da instalao

    3.1.1 componente (de uma instalao eltrica): Termo empregado para designar itens da instalao que,dependendo do contexto, podem ser materiais, acessrios, dispositivos, instrumentos, equipamentos(de gerao, converso, transformao, transmisso, armazenamento, distribuio ou utilizao deeletricidade), mquinas, conjuntos ou mesmo segmentos ou partes da instalao (por exemplo, linhaseltricas).

    3.1.2 quadro de distribuio principal: Primeiro quadro de distribuio aps a entrada da linha eltricana edificao. Naturalmente, o termo se aplica a todo quadro de distribuio que seja o nico de umaedificao.

    NOTA Ver definio de "ponto de entrada (numa edificao) (3.4.4).

    3.2 Proteo contra choques eltricos

    3.2.1 elemento condutivo ou parte condutiva: Elemento ou parte constituda de material condutor,pertencente ou no instalao, mas que no destinada normalmente a conduzir corrente eltrica.

    3.2.2 proteo bsica: Meio destinado a impedir contato com partes vivas perigosas em condiesnormais.

    3.2.3 proteo supletiva: Meio destinado a suprir a proteo contra choques eltricos quando massas oupartes condutivas acessveis tornam-se acidentalmente vivas.

    3.2.4 proteo adicional: Meio destinado a garantir a proteo contra choques eltricos em situaes de

    maior risco de perda ou anulao das medidas normalmente aplicveis, de dificuldade no atendimento plenodas condies de segurana associadas a determinada medida de proteo e/ou, ainda, em situaes oulocais em que os perigos do choque eltrico so particularmente graves.

    3.2.5 dispositivo de proteo a corrente diferencial-residual (formas abreviadas: dispositivo a correntediferencial-residual, dispositivo diferencial, dispositivo DR): Dispositivo de seccionamento mecnico ouassociao de dispositivos destinada a provocar a abertura de contatos quando a corrente diferencial-residual atinge um valor dado em condies especificadas.

    NOTA O termo dispositivo no deve ser entendido como significando um produto particular, mas sim qualquerforma possvel de se implementar a proteo diferencial-residual. So exemplos de tais formas: o interruptor, disjuntor outomada com proteo diferencial-residual incorporada, os blocos e mdulos de proteo diferencial-residual acoplveis adisjuntores, os rels e transformadores de corrente que se podem associar a disjuntores, etc.

    3.2.6 SELV (do ingls separated extra-low voltage): Sistema de extrabaixa tenso que eletricamenteseparado da terra, de outros sistemas e de tal modo que a ocorrncia de uma nica falta no resulta em riscode choque eltrico.

    3.2.7 PELV (do ingls protected extra-low voltage): Sistema de extrabaixa tenso que no eletricamente separado da terra mas que preenche, de modo equivalente, todos os requisitos de um SELV.

    3.3 Proteo contra choques eltricos e proteo contra sobretenses e perturbaeseletromagnticas

    3.3.1 eqipotencializao: Procedimento que consiste na interligao de elementos especificados,

    visando obter a eqipotencialidade necessria para os fins desejados. Por extenso, a prpria rede deelementos interligados resultante.

  • 8/8/2019 NBR 5410 2004 Corrigida 2008

    16/217

    ABNT NBR 5410:2004

    8 ABNT 2004 Todos os direitos reservados

    NOTA A eqipotencializao um recurso usado na proteo contra choques eltricos e na proteo contrasobretenses e perturbaes eletromagnticas. Uma determinada eqipotencializao pode ser satisfatria para aproteo contra choques eltricos, mas insuficiente sob o ponto de vista da proteo contra perturbaeseletromagnticas.

    3.3.2 barramento de eqipotencializao principal (BEP): Barramento destinado a servir de via deinterligao de todos os elementos incluveis na eqipotencializao principal (ver 6.4.2.1).

    NOTA A designao barramento est associada ao papel de via de interligao e no a qualquer configuraoparticular do elemento. Portanto, em princpio o BEP pode ser uma barra, uma chapa, um cabo, etc.

    3.3.3 barramento de eqipotencializao suplementar ou barramento de eqipotencializao local(BEL): Barramento destinado a servir de via de interligao de todos os elementos incluveis numaeqipotencializao suplementar ou eqipotencializao local.

    3.3.4 equipamento de tecnologia da informao (ETI): Equipamento concebido com o objetivo de:

    a) receber dados de uma fonte externa (por exemplo, via linha de entrada de dados ou via teclado);

    b) processar os dados recebidos (por exemplo, executando clculos, transformando ou registrando osdados, arquivando-os, triando-os, memorizando-os, transferindo-os); e

    c) fornecer dados de sada (seja a outro equipamento, seja reproduzindo dados ou imagens).

    NOTA Esta definio abrange uma ampla gama de equipamentos, como, por exemplo: computadores;equipamentos transceptores, concentradores e conversores de dados; equipamentos de telecomunicao e detransmisso de dados; sistemas de alarme contra incndio e intruso; sistemas de controle e automao predial, etc.

    3.4 Linhas eltricas

    3.4.1 linha (eltrica) de sinal: Linha em que trafegam sinais eletrnicos, sejam eles de telecomunicaes,

    de intercmbio de dados, de controle, de automao, etc.

    3.4.2 linha externa: Linha que entra ou sai de uma edificao, seja a linha de energia, de sinal, umatubulao de gua, de gs ou de qualquer outra utilidade.

    3.4.3 ponto de entrega: Ponto de conexo do sistema eltrico da empresa distribuidora de eletricidadecom a instalao eltrica da(s) unidade(s) consumidora(s) e que delimita as responsabilidades dadistribuidora, definidas pela autoridade reguladora.

    3.4.4 ponto de entrada (numa edificao): Ponto em que uma linha externa penetra na edificao.

    NOTAS

    1 Em particular, no caso das linhas eltricas de energia, no se deve confundir ponto de entrada com ponto deentrega. A referncia fundamental do ponto de entrada a edificao, ou seja, o corpo principal ou cada um dos blocosde uma propriedade. No caso de edificaes com pavimento em pilotis (geralmente o trreo) e nas quais a entrada dalinha eltrica externa se d no nvel do pavimento em pilotis, o ponto de entrada pode ser considerado como o ponto emque a linha penetra no compartimento de acesso edificao (hall de entrada).

    2 Alm da edificao em si, outra referncia indissocivel de ponto de entrada o barramento deeqipotencializao principal (BEP), localizado junto ou bem prximo do ponto de entrada (ver 6.4.2.1).

    3.4.5 ponto de utilizao: Ponto de uma linha eltrica destinado conexo de equipamento de utilizao.

    NOTAS

    1 Um ponto de utilizao pode ser classificado, entre outros critrios, de acordo com a tenso da linha eltrica, anatureza da carga prevista (ponto de luz, ponto para aquecedor, ponto para aparelho de ar-condicionado, etc.) e o tipo deconexo previsto (ponto de tomada, ponto de ligao direta).

  • 8/8/2019 NBR 5410 2004 Corrigida 2008

    17/217

    ABNT NBR 5410:2004

    ABNT 2004 Todos os direitos reservados 9

    2 Uma linha eltrica pode ter um ou mais pontos de utilizao.

    3 Um mesmo ponto de utilizao pode alimentar um ou mais equipamentos de utilizao.

    3.4.6 ponto de tomada: Ponto de utilizao em que a conexo do equipamento ou equipamentos a serem

    alimentados feita atravs de tomada de corrente.

    NOTAS

    1 Um ponto de tomada pode conter uma ou mais tomadas de corrente.

    2 Um ponto de tomada pode ser classificado, entre outros critrios, de acordo com a tenso do circuito queo alimenta, o nmero de tomadas de corrente nele previsto, o tipo de equipamento a ser alimentado (quandohouver algum que tenha sido especialmente previsto para utilizao do ponto) e a corrente nominal da ou dastomadas de corrente nele utilizadas.

    3.5 Servios de segurana

    3.5.1 servios de segurana: Servios essenciais, numa edificao,

    para a segurana das pessoas;

    para evitar danos ao ambiente ou aos bens.

    NOTA So exemplos de servios de segurana:

    a iluminao de segurana (iluminao de emergncia),

    bombas de incndio,

    elevadores para brigada de incndio e bombeiros,

    sistemas de alarme, como os de incndio, fumaa, CO e intruso,

    sistemas de exausto de fumaa,

    equipamentos mdicos essenciais.

    3.5.2 alimentao ou fonte normal: Alimentao ou fonte responsvel pelo fornecimento regular deenergia eltrica.

    NOTA Uma determinada alimentao pode ser a normal durante certo perodo de tempo e no ser em outro.Por exemplo, em uma instalao cujo consumo de energia eltrica suprido pela rede de distribuio pblica durante

    certos perodos do dia, mas por gerao prpria em outros, a fonte normal pode ser a rede pblica ou a gerao local,dependendo do perodo considerado.

    3.5.3 alimentao ou fonte de reserva: Alimentao ou fonte que substitui ou complementa a fontenormal.

    3.5.4 alimentao ou fonte de segurana: Alimentao ou fonte destinada a assegurar o fornecimentode energia eltrica a equipamentos essenciais para os servios de segurana.

    NOTAS (comuns a 3.5.3 e 3.5.4)

    1 O conceito de fonte de segurana est associado funo (servios de segurana) desempenhada porequipamentos que a fonte alimenta, enquanto o conceito de fonte de reserva est associado ao fato de a fontecomplementar a fonte normal ou suprir a sua falta. Como se trata de atributos distintos, que no so incompatveis, umafonte pode ser ao mesmo tempo de segurana e de reserva, desde que rena os dois atributos. Mas uma fonte dereserva destinada a alimentar exclusivamente equipamentos outros que no os de servios de segurana no pode serqualificada como de segurana.

  • 8/8/2019 NBR 5410 2004 Corrigida 2008

    18/217

    ABNT NBR 5410:2004

    10 ABNT 2004 Todos os direitos reservados

    2 Uma alimentao de segurana pode eventualmente atender a outros equipamentos, alm dos essenciais aosservios de segurana, observados os requisitos de 6.6.6.5.

    3 Esta Norma no inclui, nesta edio, prescries especficas para alimentaes de reserva destinadas a outrosservios que no os de segurana.

    4 Princpios fundamentais e determinao das caractersticas gerais

    4.1 Princpios fundamentais

    Os princpios que orientam os objetivos e as prescries desta Norma so relacionados em 4.1.1 a 4.1.15.

    4.1.1 Proteo contra choques eltricos

    As pessoas e os animais devem ser protegidos contra choques eltricos, seja o risco associado a contatoacidental com parte viva perigosa, seja a falhas que possam colocar uma massa acidentalmente sob tenso.

    4.1.2 Proteo contra efeitos trmicos

    A instalao eltrica deve ser concebida e construda de maneira a excluir qualquer risco de incndio demateriais inflamveis, devido a temperaturas elevadas ou arcos eltricos. Alm disso, em servio normal, nodeve haver riscos de queimaduras para as pessoas e os animais.

    4.1.3 Proteo contra sobrecorrentes

    As pessoas, os animais e os bens devem ser protegidos contra os efeitos negativos de temperaturas ousolicitaes eletromecnicas excessivas resultantes de sobrecorrentes a que os condutores vivos possam sersubmetidos.

    4.1.4 Circulao de correntes de falta

    Condutores que no os condutores vivos e outras partes destinadas a escoar correntes de falta devem podersuportar essas correntes sem atingir temperaturas excessivas.

    NOTAS

    1 Convm lembrar que tais partes esto sujeitas circulao desde pequenas correntes de fuga a correntes de faltadireta terra ou massa, passando por correntes de falta de intensidade inferior de uma falta direta.

    2 No caso dos condutores vivos, considera-se que sua suportabilidade s correntes de falta deve ser asseguradamediante proteo contra sobrecorrentes, como enunciado em 4.1.3.

    4.1.5 Proteo contra sobretenses

    As pessoas, os animais e os bens devem ser protegidos contra as conseqncias prejudiciais de ocorrnciasque possam resultar em sobretenses, como faltas entre partes vivas de circuitos sob diferentes tenses,fenmenos atmosfricos e manobras.

    4.1.6 Servios de segurana

    Equipamentos destinados a funcionar em situaes de emergncia, como incndios, devem ter seufuncionamento assegurado a tempo e pelo tempo julgado necessrio.

  • 8/8/2019 NBR 5410 2004 Corrigida 2008

    19/217

    ABNT NBR 5410:2004

    ABNT 2004 Todos os direitos reservados 11

    4.1.7 Desligamento de emergncia

    Sempre que forem previstas situaes de perigo em que se faa necessrio desenergizar um circuito, devemser providos dispositivos de desligamento de emergncia, facilmente identificveis e rapidamentemanobrveis.

    4.1.8 Seccionamento

    A alimentao da instalao eltrica, de seus circuitos e de seus equipamentos deve poder ser seccionadapara fins de manuteno, verificao, localizao de defeitos e reparos.

    4.1.9 Independncia da instalao eltrica

    A instalao eltrica deve ser concebida e construda livre de qualquer influncia mtua prejudicial entreinstalaes eltricas e no eltricas.

    4.1.10 Acessibilidade dos componentes

    Os componentes da instalao eltrica devem ser dispostos de modo a permitir espao suficiente tanto paraa instalao inicial quanto para a substituio posterior de partes, bem como acessibilidade para fins deoperao, verificao, manuteno e reparos.

    4.1.11 Seleo dos componentes

    Os componentes da instalao eltrica devem ser conforme as normas tcnicas aplicveis e possuircaractersticas compatveis com as condies eltricas, operacionais e ambientais a que forem submetidos.Se o componente selecionado no reunir, originalmente, essas caractersticas, devem ser providas medidascompensatrias, capazes de compatibiliz-las com as exigncias da aplicao.

    4.1.12 Preveno de efeitos danosos ou indesejados

    Na seleo dos componentes, devem ser levados em considerao os efeitos danosos ou indesejados que ocomponente possa apresentar, em servio normal (incluindo operaes de manobra), sobre outroscomponentes ou na rede de alimentao. Entre as caractersticas e fenmenos suscetveis de gerarperturbaes ou comprometer o desempenho satisfatrio da instalao podem ser citados:

    o fator de potncia;

    as correntes iniciais ou de energizao;

    o desequilbrio de fases;

    as harmnicas.

    4.1.13 Instalao dos componentes

    Toda instalao eltrica requer uma cuidadosa execuo por pessoas qualificadas, de forma a assegurar,entre outros objetivos, que:

    as caractersticas dos componentes da instalao, como indicado em 4.1.11, no sejamcomprometidas durante sua montagem;

    os componentes da instalao, e os condutores em particular, fiquem adequadamente identificados;

    nas conexes, o contato seja seguro e confivel; os componentes sejam instalados preservando-se as condies de resfriamento previstas;

  • 8/8/2019 NBR 5410 2004 Corrigida 2008

    20/217

    ABNT NBR 5410:2004

    12 ABNT 2004 Todos os direitos reservados

    os componentes da instalao suscetveis de produzir temperaturas elevadas ou arcos eltricosfiquem dispostos ou abrigados de modo a eliminar o risco de ignio de materiais inflamveis; e

    as partes externas de componentes sujeitas a atingir temperaturas capazes de lesionar pessoasfiquem dispostas ou abrigadas de modo a garantir que as pessoas no corram risco de contatos

    acidentais com essas partes.

    4.1.14 Verificao da instalao

    As instalaes eltricas devem ser inspecionadas e ensaiadas antes de sua entrada em funcionamento, bemcomo aps cada reforma, com vista a assegurar que elas foram executadas de acordo com esta Norma.

    4.1.15 Qualificao profissional

    O projeto, a execuo, a verificao e a manuteno das instalaes eltricas devem ser confiados somentea pessoas qualificadas a conceber e executar os trabalhos em conformidade com esta Norma.

    4.2 Determinao das caractersticas gerais

    Na concepo de uma instalao eltrica devem ser determinadas as seguintes caractersticas:

    a) utilizao prevista e demanda (ver 4.2.1);

    b) esquema de distribuio (ver 4.2.2);

    c) alimentaes disponveis (ver 4.2.3);

    d) necessidade de servios de segurana e de fontes apropriadas (ver 4.2.4);

    e) exigncias quanto diviso da instalao (ver 4.2.5);

    f) influncias externas s quais a instalao for submetida (ver 4.2.6);

    g) riscos de incompatibilidade e de interferncias (ver 4.2.7);

    h) requisitos de manuteno (ver 4.2.8).

    4.2.1 Utilizao e demanda Potncia de alimentao

    4.2.1.1 Generalidades

    4.2.1.1.1 A determinao da potncia de alimentao essencial para a concepo econmica e segura

    de uma instalao, dentro de limites adequados de elevao de temperatura e de queda de tenso.

    4.2.1.1.2 Na determinao da potncia de alimentao de uma instalao ou de parte de uma instalaodevem ser computados os equipamentos de utilizao a serem alimentados, com suas respectivas potnciasnominais e, em seguida, consideradas as possibilidades de no-simultaneidade de funcionamento destesequipamentos, bem como capacidade de reserva para futuras ampliaes.

    4.2.1.2 Previso de carga

    A previso de carga de uma instalao deve ser feita obedecendo-se s prescries de 4.2.1.2.1 a 4.2.1.2.3.

  • 8/8/2019 NBR 5410 2004 Corrigida 2008

    21/217

    ABNT NBR 5410:2004

    ABNT 2004 Todos os direitos reservados 13

    4.2.1.2.1 Geral:

    a) a carga a considerar para um equipamento de utilizao a potncia nominal por ele absorvida, dadapelo fabricante ou calculada a partir da tenso nominal, da corrente nominal e do fator de potncia;

    b) nos casos em que for dada a potncia nominal fornecida pelo equipamento (potncia de sada), e no aabsorvida, devem ser considerados o rendimento e o fator de potncia.

    4.2.1.2.2 Iluminao:

    a) as cargas de iluminao devem ser determinadas como resultado da aplicao da ABNT NBR 5413;

    b) para os aparelhos fixos de iluminao a descarga, a potncia nominal a ser considerada deve incluir apotncia das lmpadas, as perdas e o fator de potncia dos equipamentos auxiliares.

    NOTA Em 9.5.2.1 so fixados critrios mnimos para pontos de iluminao em locais de habitao.

    4.2.1.2.3 Pontos de tomada:

    a) em locais de habitao, os pontos de tomada devem ser determinados e dimensionados de acordo com9.5.2.2;

    b) em halls de servio, salas de manuteno e salas de equipamentos, tais como casas de mquinas, salasde bombas, barriletes e locais anlogos, deve ser previsto no mnimo um ponto de tomada de uso geral.Aos circuitos terminais respectivos deve ser atribuda uma potncia de no mnimo 1000 VA;

    c) quando um ponto de tomada for previsto para uso especfico, deve ser a ele atribuda uma potncia igual potncia nominal do equipamento a ser alimentado ou soma das potncias nominais dosequipamentos a serem alimentados. Quando valores precisos no forem conhecidos, a potnciaatribuda ao ponto de tomada deve seguir um dos dois seguintes critrios:

    potncia ou soma das potncias dos equipamentos mais potentes que o ponto pode vir a alimentar, ou

    potncia calculada com base na corrente de projeto e na tenso do circuito respectivo;

    d) os pontos de tomada de uso especfico devem ser localizados no mximo a 1,5 m do ponto previsto paraa localizao do equipamento a ser alimentado;

    e) os pontos de tomada destinados a alimentar mais de um equipamento devem ser providos com aquantidade adequada de tomadas.

    4.2.2 Esquema de distribuio

    O esquema de distribuio pode ser classificado de acordo com os seguintes critrios:

    a) esquema de condutores vivos;

    b) esquema de aterramento.

    4.2.2.1 Esquema de condutores vivos

    So considerados os seguintes esquemas de condutores vivos:

    a) corrente alternada:

    monofsico a dois condutores;

    monofsico a trs condutores;

  • 8/8/2019 NBR 5410 2004 Corrigida 2008

    22/217

    ABNT NBR 5410:2004

    14 ABNT 2004 Todos os direitos reservados

    bifsico a trs condutores;

    trifsico a trs condutores;

    trifsico a quatro condutores;

    b) corrente contnua:

    dois condutores;

    trs condutores.

    4.2.2.2 Esquema de aterramento

    Nesta Norma so considerados os esquemas de aterramento descritos em 4.2.2.2.1 a 4.2.2.3, cabendo asseguintes observaes sobre as ilustraes e smbolos utilizados:

    a) as figuras 1 a 5, que ilustram os esquemas de aterramento, devem ser interpretadas de forma genrica.Elas utilizam como exemplo sistemas trifsicos. As massas indicadas no simbolizam um nico, mas simqualquer nmero de equipamentos eltricos. Alm disso, as figuras no devem ser vistas com conotaoespacial restrita. Deve-se notar, neste particular, que como uma mesma instalao pode eventualmenteabranger mais de uma edificao, as massas devem necessariamente compartilhar o mesmo eletrodo deaterramento, se pertencentes a uma mesma edificao, mas podem, em princpio, estar ligadas aeletrodos de aterramento distintos, se situadas em diferentes edificaes, com cada grupo de massasassociado ao eletrodo de aterramento da edificao respectiva. Nas figuras so utilizados os seguintessmbolos:

    b) na classificao dos esquemas de aterramento utilizada a seguinte simbologia:

    primeira letra Situao da alimentao em relao terra:

    T = um ponto diretamente aterrado;

    I = isolao de todas as partes vivas em relao terra ou aterramento de um ponto atravs deimpedncia;

    segunda letra Situao das massas da instalao eltrica em relao terra:

    T = massas diretamente aterradas, independentemente do aterramento eventual de um ponto daalimentao;

    N = massas ligadas ao ponto da alimentao aterrado (em corrente alternada, o ponto aterrado normalmente o ponto neutro);

    outras letras (eventuais) Disposio do condutor neutro e do condutor de proteo:

    S = funes de neutro e de proteo asseguradas por condutores distintos;

    C = funes de neutro e de proteo combinadas em um nico condutor (condutor PEN).

  • 8/8/2019 NBR 5410 2004 Corrigida 2008

    23/217

    ABNT NBR 5410:2004

    ABNT 2004 Todos os direitos reservados 15

    4.2.2.2.1 Esquema TN

    O esquema TN possui um ponto da alimentao diretamente aterrado, sendo as massas ligadas a esseponto atravs de condutores de proteo. So consideradas trs variantes de esquema TN, de acordo com adisposio do condutor neutro e do condutor de proteo, a saber:

    a) esquema TN-S, no qual o condutor neutro e o condutor de proteo so distintos (figura 1);

    b) esquema TN-C-S, em parte do qual as funes de neutro e de proteo so combinadas em um nicocondutor (figura 2);

    c) esquema TN-C, no qual as funes de neutro e de proteo so combinadas em um nico condutor, natotalidade do esquema (figura 3).

    Figura 1 Esquema TN-S

    NOTA As funes de neutro e de condutor de proteo so combinadas num nico condutor em parte do esquema.

    Figura 2 Esquema TN-C-S

  • 8/8/2019 NBR 5410 2004 Corrigida 2008

    24/217

    ABNT NBR 5410:2004

    16 ABNT 2004 Todos os direitos reservados

    NOTA As funes de neutro e de condutor de proteo so combinadas num nico condutor, na totalidade doesquema.

    Figura 3 Esquema TN-C

    4.2.2.2.2 Esquema TT

    O esquema TT possui um ponto da alimentao diretamente aterrado, estando as massas da instalaoligadas a eletrodo(s) de aterramento eletricamente distinto(s) do eletrodo de aterramento da alimentao(figura 4).

    Figura 4 Esquema TT

    4.2.2.2.3 Esquema IT

    No esquema IT todas as partes vivas so isoladas da terra ou um ponto da alimentao aterrado atravs de

    impedncia (figura 5). As massas da instalao so aterradas, verificando-se as seguintes possibilidades:

    massas aterradas no mesmo eletrodo de aterramento da alimentao, se existente; e

    massas aterradas em eletrodo(s) de aterramento prprio(s), seja porque no h eletrodo deaterramento da alimentao, seja porque o eletrodo de aterramento das massas independente doeletrodo de aterramento da alimentao.

  • 8/8/2019 NBR 5410 2004 Corrigida 2008

    25/217

    ABNT NBR 5410:2004

    ABNT 2004 Todos os direitos reservados 17

    1) O neutro pode ser ou no distribudo;

    A = sem aterramento da alimentao;

    B = alimentao aterrada atravs de impedncia;

    B.1 = massas aterradas em eletrodos separados e independentes do eletrodo de aterramento da alimentao;

    B.2 = massas coletivamente aterradas em eletrodo independente do eletrodo de aterramento da alimentao;

    B.3 = massas coletivamente aterradas no mesmo eletrodo da alimentao.

    Figura 5 Esquema IT

    4.2.3 Alimentaes

    4.2.3.1 Devem ser determinadas as seguintes caractersticas das fontes de suprimento de energia comas quais a instalao for provida:

    a) natureza da corrente e freqncia;

    b) valor da tenso nominal;

    c) valor da corrente de curto-circuito presumida no ponto de suprimento;

    d) possibilidade de atendimento dos requisitos da instalao, incluindo a demanda de potncia.NOTA As faixas de tenso em corrente alternada ou contnua em que devem ser classificadas as instalaes,conforme a tenso nominal, so dadas no anexo A.

  • 8/8/2019 NBR 5410 2004 Corrigida 2008

    26/217

    ABNT NBR 5410:2004

    18 ABNT 2004 Todos os direitos reservados

    4.2.3.2 As caractersticas relacionadas em 4.2.3.1 devem ser obtidas junto empresa distribuidora deenergia eltrica, no que se refere ao suprimento via rede pblica de distribuio, e devem ser determinadas,quando se tratar de fonte prpria.

    4.2.4 Servios de segurana

    Quando for imposta a necessidade de servios de segurana, as fontes de alimentao para tais serviosdevem possuir capacidade, confiabilidade e disponibilidade adequadas ao funcionamento especificado.Em 6.6 so apresentadas prescries para a alimentao de servios de segurana.

    NOTA Esta Norma no inclui, nesta edio, prescries especficas para alimentaes de reserva destinadas aoutros servios que no os de segurana.

    4.2.5 Diviso da instalao

    4.2.5.1 A instalao deve ser dividida em tantos circuitos quantos necessrios, devendo cada circuito serconcebido de forma a poder ser seccionado sem risco de realimentao inadvertida atravs de outro circuito.

    4.2.5.2 A diviso da instalao em circuitos deve ser de modo a atender, entre outras, s seguintesexigncias:

    a) segurana por exemplo, evitando que a falha em um circuito prive de alimentao toda uma rea;

    b) conservao de energia por exemplo, possibilitando que cargas de iluminao e/ou de climatizaosejam acionadas na justa medida das necessidades;

    c) funcionais por exemplo, viabilizando a criao de diferentes ambientes, como os necessrios emauditrios, salas de reunies, espaos de demonstrao, recintos de lazer, etc.;

    d) de produo por exemplo, minimizando as paralisaes resultantes de uma ocorrncia;

    e) de manuteno por exemplo, facilitando ou possibilitando aes de inspeo e de reparo.

    4.2.5.3 Devem ser previstos circuitos distintos para partes da instalao que requeiram controleespecfico, de tal forma que estes circuitos no sejam afetados pelas falhas de outros (por exemplo, circuitosde superviso predial).

    4.2.5.4 Na diviso da instalao devem ser consideradas tambm as necessidades futuras.As ampliaes previsveis devem se refletir no s na potncia de alimentao, como tratado em 4.2.1, mastambm na taxa de ocupao dos condutos e dos quadros de distribuio.

    4.2.5.5 Os circuitos terminais devem ser individualizados pela funo dos equipamentos de utilizaoque alimentam. Em particular, devem ser previstos circuitos terminais distintos para pontos de iluminao e

    para pontos de tomada.

    NOTA Para locais de habitao, ver tambm 9.5.3.

    4.2.5.6 As cargas devem ser distribudas entre as fases, de modo a obter-se o maior equilbrio possvel.

    4.2.5.7 Quando a instalao comportar mais de uma alimentao (rede pblica, gerao local, etc.), adistribuio associada especificamente a cada uma delas deve ser disposta separadamente e de formaclaramente diferenciada das demais. Em particular, no se admite que componentes vinculadosespecificamente a uma determinada alimentao compartilhem, com elementos de outra alimentao,quadros de distribuio e linhas, incluindo as caixas dessas linhas, salvo as seguintes excees:

    a) circuitos de sinalizao e comando, no interior de quadros;

    b) conjuntos de manobra especialmente projetados para efetuar o intercmbio das fontes de alimentao;

  • 8/8/2019 NBR 5410 2004 Corrigida 2008

    27/217

    ABNT NBR 5410:2004

    ABNT 2004 Todos os direitos reservados 19

    c) linhas abertas e nas quais os condutores de uma e de outra alimentao sejam adequadamenteidentificados.

    4.2.6 Classificao das influncias externas

    Esta subseo estabelece uma classificao e uma codificao das influncias externas que devem serconsideradas na concepo e na execuo das instalaes eltricas. Cada condio de influncia externa designada por um cdigo que compreende sempre um grupo de duas letras maisculas e um nmero, comodescrito a seguir:

    a) a primeira letra indica a categoria geral da influncia externa:

    A = meio ambiente;

    B = utilizao;

    C = construo das edificaes;

    b) a segunda letra (A, B, C, ...) indica a natureza da influncia externa;

    c) o nmero (1, 2, 3, ...) indica a classe de cada influncia externa.

    NOTAS

    1 A codificao indicada nesta subseo no destinada marcao dos componentes. Essa questo (marcao doscomponentes) tratada nas normas dos prprios componentes e, de forma integrada, em normas mais gerais como, porexemplo, a que define e classifica os graus de proteo providos por invlucros (ver IEC 60529) ou a que define asclasses de proteo contra choques eltricos (ver IEC 61140).

    2 Como h uma tendncia de se associar a idia de influncias externas predominantemente a fatores comotemperatura ambiente, condies climticas, presena de gua e solicitaes mecnicas, importante destacar que a

    classificao aqui apresentada cobre uma gama muito mais extensa de variveis de influncia, todas tendo seu peso emaspectos como seleo dos componentes, adequao de medidas de proteo, etc. Por exemplo, a qualificao daspessoas (sua conscincia e seu preparo para lidar com os riscos da eletricidade), situaes que reforam ou prejudicama resistncia eltrica do corpo humano (pele seca, pele molhada, imerso, etc.) e o nvel de contato das pessoas com opotencial da terra so influncias externas que podem decidir se uma medida de proteo contra choques ou noaceitvel em determinado local, dependendo de como essas condies de influncias externas a se apresentam.

    4.2.6.1 Meio ambiente

    4.2.6.1.1 Temperatura ambiente

    A temperatura ambiente (ver tabela 1) a considerar para um componente a temperatura no local onde deveser instalado, includa a influncia dos demais componentes instalados no local e em funcionamento, e

    excluda a contribuio trmica do prprio componente considerado.

  • 8/8/2019 NBR 5410 2004 Corrigida 2008

    28/217

  • 8/8/2019 NBR 5410 2004 Corrigida 2008

    29/217

    ABNT NBR 5410:2004

    ABNT 2004 Todos os direitos reservados 21

    Tabela 2 (concluso)

    Cdigo

    Caractersticas

    Aplicaes e exemplos

    Temperaturado ar

    C

    Umidaderelativa

    %

    Umidade

    absoluta g/m

    Limiteinferior

    Limitesuperior

    Limiteinferior

    Limitesuperior

    Limiteinferior

    Limitesuperior

    AB5 + 5 + 40 5 85 1 25Locais abrigados comtemperatura ambientecontrolada

    AB6 + 5 + 60 10 100 1 35

    Ambientes internos eexternos com temperaturasextremamente altas,protegidos contra baixastemperaturas ambientes.

    Ocorrncia de radiaosolar e de calor

    AB7 25 + 55 10 100 0,5 29

    Ambientes internos eabrigados sem controle datemperatura e da umidade.Podem ter aberturas para oexterior e so sujeitos aradiao solar

    AB8 50 + 40 15 100 0,04 36

    Ambientes externos e semproteo contra intempries,sujeitos a altas e baixastemperaturas

    NOTAS

    1 Todos os valores especificados so limites, com baixa probabilidade de serem excedidos.

    2 Os valores de umidade relativa, inferiores e superiores, so limitados pelos valorescorrespondentes de umidade absoluta. O apndice B da IEC 60364-5-51:2001 traz informaes sobre ainterdependncia da temperatura do ar, umidade relativa e umidade absoluta para as classes decondies climticas especificadas.

    4.2.6.1.3 Altitude

    Conforme tabela 3.

    Tabela 3 Altitude

    Cdigo Classificao Caractersticas Aplicaes e exemplos

    AC1 Baixa 2 000 m Para alguns componentes,podem ser necessriasmedidas especiais a partirde 1 000 m de altitude

    AC2 Alta > 2 000 m

    4.2.6.1.4 Presena de gua

    Conforme tabela 4.

  • 8/8/2019 NBR 5410 2004 Corrigida 2008

    30/217

    ABNT NBR 5410:2004

    22 ABNT 2004 Todos os direitos reservados

    Tabela 4 Presena de gua

    Cdigo Classificao Caractersticas Aplicaes e exemplos

    AD1 DesprezvelA probabilidade depresena de gua remota

    Locais em que as paredes geralmente noapresentam umidade, mas podemapresent-la durante curtos perodos, esecam rapidamente com uma boa aerao

    AD2 GotejamentoPossibilidade degotejamento de gua navertical

    Locais em que a umidade se condensaocasionalmente, sob forma de gotas degua, ou em que h presena ocasional devapor de gua

    AD3 PrecipitaoPossibilidade de chuvacaindo em ngulo mximode 60o com a vertical

    Locais em que a gua forma uma pelculacontnua nas paredes e/ou pisos

    AD4 Asperso Possibilidade de chuva dequalquer direo

    A asperso corresponde ao efeito de umachuva vinda de qualquer direo. So

    exemplos de componentes sujeitos aasperso certas luminrias de uso externo epainis eltricos de canteiros de obras aotempo

    AD5 JatosPossibilidade de jatos degua sob presso, emqualquer direo

    Locais em que ocorrem lavagens com guasob presso, como passeios pblicos, reasde lavagem de veculos, etc.

    AD6 OndasPossibilidade de ondas degua

    Locais situados beira-mar, como praias,piers, ancoradouros, etc.

    AD7 ImersoPossibilidade de imersoem gua, parcial ou total,de modo intermitente

    Locais sujeitos a inundao e/ou onde agua possa se elevar pelo menos a 15 cm

    acima do ponto mais alto do componente dainstalao eltrica, estando sua parte maisbaixa a no mximo 1 m abaixo da superfcieda gua

    AD8 SubmersoSubmerso total em gua,de modo permanente

    Locais onde os componentes da instalaoeltrica sejam totalmente submersos, sobuma presso superior a 10 kPa (0,1 bar, ou1 mca)

    4.2.6.1.5 Presena de corpos slidos

    Conforme tabela 5.

    Tabela 5 Presena de corpos slidos

    Cdigo Classificao Caractersticas Aplicaes e exemplos

    AE1 DesprezvelAusncia de poeira emquantidade aprecivele de corpos estranhos

    AE2 Pequenos objetos

    Presena de corposslidos cuja menordimenso seja igual ousuperior a 2,5 mm1)

    Ferramentas, materialgranulado, etc.

  • 8/8/2019 NBR 5410 2004 Corrigida 2008

    31/217

    ABNT NBR 5410:2004

    ABNT 2004 Todos os direitos reservados 23

    Tabela 5 (concluso)

    Cdigo Classificao Caractersticas Aplicaes e exemplos

    AE3 Objetos muito pequenos

    Presena de corposslidos cuja menordimenso seja igual ousuperior a 1 mm1)

    Fios metlicos, arames,etc.

    AE4 Poeira levePresena de levedeposio de poeira

    Deposio de poeira maiorque 10 mg/m2 e no mximoigual a 35 mg/m2 por dia

    AE5 Poeira moderadaPresena de mdiadeposio de poeira

    Deposio de poeira maiorque 35 mg/m2 e no mximoigual a 350 mg/m2 por dia

    AE6 Poeira intensaPresena de elevadadeposio de poeira

    Deposio de poeira maiorque 350 mg/m2 e nomximo igual a 1000 mg/m2

    por diaNOTA Nas condies AE2 e AE3 pode existir poeira, desde que esta no tenha influnciasignificativa sobre os componentes eltricos.

    4.2.6.1.6 Presena de substncias corrosivas ou poluentes

    Conforme tabela 6.

    Tabela 6 Presena de substncias corrosivas ou poluentes

    Cdigo Classificao Caractersticas Aplicaes e exemplos

    AF1 Desprezvel

    A quantidade ou

    natureza dosagentes corrosivosou poluentes no significativa

    AF2 Atmosfrica

    Presenasignificativa deagentes corrosivosou poluentes deorigem atmosfrica

    Instalaes prximas da orla martimaou de estabelecimentos industriais queproduzam poluio atmosfricasignificativa, tais como indstriasqumicas, fbricas de cimento, etc.Este tipo de poluio provmprincipalmente da emisso de poeirasabrasivas, isolantes ou condutivas

    AF3Intermitente ouacidental

    Presenaintermitente ouacidental deprodutos qumicoscorrosivos oupoluentes de usocorrente

    Locais onde se manipulam produtos

    qumicos em pequenas quantidades eonde o contato desses produtos com oscomponentes da instalao sejameramente acidental. Tais condiespodem ocorrer em laboratrios defbricas e outros, ou em locais onde seutilizam hidrocarbonetos (centrais decalefao, oficinas, etc.)

    AF4 Permanente

    Presenapermanente deprodutos qumicoscorrosivos oupoluentes em

    quantidadessignificativas

    Indstrias qumicas, etc.

  • 8/8/2019 NBR 5410 2004 Corrigida 2008

    32/217

    ABNT NBR 5410:2004

    24 ABNT 2004 Todos os direitos reservados

    4.2.6.1.7 Solicitaes mecnicas

    Conforme tabela 7.

    Tabela 7 Solicitaes mecnicas

    Cdigo

    Classificao Caractersticas Aplicaes e exemplos

    Impactos (AG)

    AG1 FracosImpactos iguais ou inferiores a0,225 J

    Locais domsticos, escritrios(condies de uso domstico eanlogas)

    AG2 Mdios Impactos iguais ou inferiores a 2 J Condies industriais normais

    AG3 Severos Impactos iguais ou inferiores a 20 J Condies industriais severas

    Vibraes (AH)

    AH1 FracasNenhuma vibrao(es)eventual(ais) sem influnciasignificativa

    Condies domsticas e anlogas, ondeos efeitos das vibraes podem sergeralmente desprezados

    AH2 Mdias

    Vibraes com freqnciascompreendidas entre 10 Hz e50 Hz e amplitude igual ou inferiora 0,15 mm

    Condies industriais normais

    AH3 Severas

    Vibraes com freqnciascompreendidas entre 10 Hz e150 Hz e amplitude igual ou inferiora 0,35 mm

    Condies industriais severas

    4.2.6.1.8 Presena de flora e mofo

    Conforme tabela 8.

    Tabela 8 Presena de flora e mofo

    Cdigo Classificao Caractersticas Aplicaes e exemplos

    AK1 DesprezvelSem risco de danosdevidos flora ou aomofo

    AK2 PrejudicialRisco de efeitosprejudiciais

    Os riscos dependem dascondies locais e danatureza da flora. Pode-sedividi-los em riscos devidosao desenvolvimentoprejudicial da vegetao eriscos devidos suaabundncia

    4.2.6.1.9 Presena de fauna

    Conforme tabela 9.

  • 8/8/2019 NBR 5410 2004 Corrigida 2008

    33/217

    ABNT NBR 5410:2004

    ABNT 2004 Todos os direitos reservados 25

    Tabela 9 Presena de fauna

    Cdigo Classificao Caractersticas Aplicaes e exemplos

    AL1 DesprezvelSem risco de danos

    devidos fauna

    AL2 Prejudicial

    Risco de efeitosprejudiciais devidos fauna(insetos, pssaros,pequenos animais)

    Os riscos dependem danatureza da fauna. Pode-sedividi-los em: perigosdevidos a insetos emquantidades prejudiciais oude natureza agressiva;presena de pequenosanimais ou de pssaros emquantidades prejudiciais oude natureza agressiva

    4.2.6.1.10 Influncias eletromagnticas, eletrostticas ou ionizantes

    Conforme tabelas 10 a 13.

    Tabela 10 Fenmenos eletromagnticos de baixa freqncia (conduzidos ou radiados)

    Cdigo Classificao Caractersticas Aplicaes e exemplos Referncias

    Harmnicas e inter-harmnicas (AM1)

    AM1-1 Nvel controlado Situao controladaAparelhos eletromdicosInstrumentos de medio

    Abaixo da tabela 1daIEC 61000-2-2:2002

    AM1-2 Nvel normal Redes de baixatenso

    Habitaes

    Locais comerciaisIndstria leve

    Dentro do estipulado

    na tabela 1 daIEC 61000-2-2:2002

    AM1-3 Nvel alto Redes poludas

    Indstrias ou grandesprdios comerciaisalimentados portransformao AT/BTdedicada

    Localmente acima databela 1 daIEC 61000-2-2:2002

    Tenses de sinalizao (tenses sobrepostas para fins de telecomando) (AM2)

    AM2-1 Nvel controladoSomente sinaisresiduais

    Instalaes protegidas ouparte protegida de umainstalao

    Inferior aoespecificado abaixo

    AM2-2 Nvel mdio