Clima e Conforto térmico - fau.usp.br - Aula... · aut0276 desempenho tÉrmico, arquitetura e...

30
AUT0276 DESEMPENHO TÉRMICO, ARQUITETURA E URBANISMO Clima e Conforto térmico Profa. Dra. Denise Helena Silva Duarte, Prof. Dr. Leonardo Marques Monteiro, Prof. Dra. Ranny Loureiro Xavier Nascimento Michalski

Transcript of Clima e Conforto térmico - fau.usp.br - Aula... · aut0276 desempenho tÉrmico, arquitetura e...

Page 1: Clima e Conforto térmico - fau.usp.br - Aula... · aut0276 desempenho tÉrmico, arquitetura e urbanismo modelo adaptativo ashrae 55 (2004, 2010, 2013) aut0276 desempenho tÉrmico,

AUT0276 DESEMPENHO TÉRMICO, ARQUITETURA E URBANISMO

Clima e Conforto térmico

Profa. Dra. Denise Helena Silva Duarte, Prof. Dr. Leonardo Marques Monteiro, Prof. Dra. Ranny Loureiro Xavier Nascimento Michalski

Page 2: Clima e Conforto térmico - fau.usp.br - Aula... · aut0276 desempenho tÉrmico, arquitetura e urbanismo modelo adaptativo ashrae 55 (2004, 2010, 2013) aut0276 desempenho tÉrmico,

AUT0276 DESEMPENHO TÉRMICO, ARQUITETURA E URBANISMO

CONFORTO

quanto maior for o esforço de adaptação

maior será a sensação de desconforto

Page 3: Clima e Conforto térmico - fau.usp.br - Aula... · aut0276 desempenho tÉrmico, arquitetura e urbanismo modelo adaptativo ashrae 55 (2004, 2010, 2013) aut0276 desempenho tÉrmico,

AUT0276 DESEMPENHO TÉRMICO, ARQUITETURA E URBANISMO

CONFORTO TÉRMICO

• Variáveis envolvidas na transferência de calor

• Variáveis do clima exterior

• Variáveis do conforto humano

Page 4: Clima e Conforto térmico - fau.usp.br - Aula... · aut0276 desempenho tÉrmico, arquitetura e urbanismo modelo adaptativo ashrae 55 (2004, 2010, 2013) aut0276 desempenho tÉrmico,

AUT0264 CONFORTO AMBIENTAL IV – TÉRMICA

Mecanismos de troca de calor

• Trocas térmicas sensíveis: envolvem diferença de temperatura

– Convecção

– Radiação

– Condução

• Trocas térmicas latentes: envolvem mudança de estado

– Evaporação

– Condensação

Page 5: Clima e Conforto térmico - fau.usp.br - Aula... · aut0276 desempenho tÉrmico, arquitetura e urbanismo modelo adaptativo ashrae 55 (2004, 2010, 2013) aut0276 desempenho tÉrmico,

AUT0276 DESEMPENHO TÉRMICO, ARQUITETURA E URBANISMO

Variáveis do clima exterior

1. Temperatura (K, ºF, ºC, ºR)

– do ar

– superficial

2. Umidade

– relativa (%)

– específica (g de vapor d’água/kg de ar seco)

3. Radiação solar

– direta e difusa (W/m2)

– insolação (h)

4. Vento

– direção (graus)

– velocidade (m/s, Km/h, nós)

Page 6: Clima e Conforto térmico - fau.usp.br - Aula... · aut0276 desempenho tÉrmico, arquitetura e urbanismo modelo adaptativo ashrae 55 (2004, 2010, 2013) aut0276 desempenho tÉrmico,

AUT0276 DESEMPENHO TÉRMICO, ARQUITETURA E URBANISMO

Variáveis do conforto 1. Metabolismo (MET)

2. Vestimenta (CLO)

3. Parâmetros que descrevem

termicamente o ambiente

– Temperatura do ar

– Temperatura radiante média

– Velocidade do ar

– Umidade do ar

Fonte: LAMBERTS. Roberto, et al. Eficiência

Energética na Arquitetura. São Paulo

Page 7: Clima e Conforto térmico - fau.usp.br - Aula... · aut0276 desempenho tÉrmico, arquitetura e urbanismo modelo adaptativo ashrae 55 (2004, 2010, 2013) aut0276 desempenho tÉrmico,

AUT0276 DESEMPENHO TÉRMICO, ARQUITETURA E URBANISMO

BALANÇO TÉRMICO

M = + CV + R + EV

M – metabolismo

CV – trocas por convecção

R – trocas por radiação

EV – trocas evaporativas

Page 8: Clima e Conforto térmico - fau.usp.br - Aula... · aut0276 desempenho tÉrmico, arquitetura e urbanismo modelo adaptativo ashrae 55 (2004, 2010, 2013) aut0276 desempenho tÉrmico,

AUT0276 DESEMPENHO TÉRMICO, ARQUITETURA E URBANISMO

TROCAS TÉRMICAS

CV – trocas por convecção

- temperatura do ar

- velocidade do ar

R – trocas por radiação

- temperatura radiante

EV – trocas evaporativas

- temperatura do ar

- umidade do ar

- velocidade do ar

Page 9: Clima e Conforto térmico - fau.usp.br - Aula... · aut0276 desempenho tÉrmico, arquitetura e urbanismo modelo adaptativo ashrae 55 (2004, 2010, 2013) aut0276 desempenho tÉrmico,

AUT0276 DESEMPENHO TÉRMICO, ARQUITETURA E URBANISMO

Adaptação do corpo humano ao meio

Perdas de Calor pelo Corpo Humano

Metabolismo – Interno Externo – Trocas de calor

(Pele) Temperatura do ar

Temperatura radiante

Umidade do ar

Velocidade do ar

Convecção (~40%)

Condução (geralmente mínima)

Radiação (~40 %) Evaporação

(~20%)

Page 10: Clima e Conforto térmico - fau.usp.br - Aula... · aut0276 desempenho tÉrmico, arquitetura e urbanismo modelo adaptativo ashrae 55 (2004, 2010, 2013) aut0276 desempenho tÉrmico,

AUT0276 DESEMPENHO TÉRMICO, ARQUITETURA E URBANISMO

ESTÍMULOS SENSAÇÕES

O grau de perturbação ou conforto depende de estímulos e sensações

O estímulo é objetivo | A sensação é subjetiva

Temperatura do ar Umidade do ar Velocidade do ar Temperatura radiante

(Objetivos, quantificáveis) (Subjetivas, não quantificáveis)

Depende da experiência anterior

ESTÍMULOS E SENSAÇÕES

Page 11: Clima e Conforto térmico - fau.usp.br - Aula... · aut0276 desempenho tÉrmico, arquitetura e urbanismo modelo adaptativo ashrae 55 (2004, 2010, 2013) aut0276 desempenho tÉrmico,

AUT0276 DESEMPENHO TÉRMICO, ARQUITETURA E URBANISMO

ADAPTAÇÃO FISIOLÓGICA - “ACLIMATAÇÃO”

Respostas biológicas que resultam de prolongada exposição as condições térmicas características e relativamente extremas.

Page 12: Clima e Conforto térmico - fau.usp.br - Aula... · aut0276 desempenho tÉrmico, arquitetura e urbanismo modelo adaptativo ashrae 55 (2004, 2010, 2013) aut0276 desempenho tÉrmico,

AUT0276 DESEMPENHO TÉRMICO, ARQUITETURA E URBANISMO

ADAPTAÇÃO PSICOLÓGICA

Diz respeito a uma percepção alterada das condições físicas devido a experiências passadas e expectativas

Page 13: Clima e Conforto térmico - fau.usp.br - Aula... · aut0276 desempenho tÉrmico, arquitetura e urbanismo modelo adaptativo ashrae 55 (2004, 2010, 2013) aut0276 desempenho tÉrmico,

AUT0276 DESEMPENHO TÉRMICO, ARQUITETURA E URBANISMO

Aceitação do ambiente por questões sociais e hábitos culturais

ADAPTAÇÃO SÓCIO-CULTURAL

Page 14: Clima e Conforto térmico - fau.usp.br - Aula... · aut0276 desempenho tÉrmico, arquitetura e urbanismo modelo adaptativo ashrae 55 (2004, 2010, 2013) aut0276 desempenho tÉrmico,

AUT0276 DESEMPENHO TÉRMICO, ARQUITETURA E URBANISMO

ADAPTAÇÃO COMPORTAMENTAL

Ação consciente ou inconsciente que uma pessoa poderia fazer para alterar o seu equilíbrio térmico corporal. Mudança de vestuário, acionamento de ventiladores, etc.

Page 15: Clima e Conforto térmico - fau.usp.br - Aula... · aut0276 desempenho tÉrmico, arquitetura e urbanismo modelo adaptativo ashrae 55 (2004, 2010, 2013) aut0276 desempenho tÉrmico,

AUT0276 DESEMPENHO TÉRMICO, ARQUITETURA E URBANISMO

Índices de conforto

Índices de Conforto: tendam englobar em um único fator todas as variáveis.

Primeiros estudos: ASHVE (1916) - rendimento do operário na indústria

Índice de conforto de Fanger: ISO 7730 (2005); ASHRAE 55 (2004)

Modelos adaptativos: ASHRAE 55 (2004, 2010, 2013); BS EN 1525 (2007)

Page 16: Clima e Conforto térmico - fau.usp.br - Aula... · aut0276 desempenho tÉrmico, arquitetura e urbanismo modelo adaptativo ashrae 55 (2004, 2010, 2013) aut0276 desempenho tÉrmico,

AUT0276 DESEMPENHO TÉRMICO, ARQUITETURA E URBANISMO

ET: Temperatura Efetiva - Houghten et al. (1923) / Vernon & Warner (1932)

Page 17: Clima e Conforto térmico - fau.usp.br - Aula... · aut0276 desempenho tÉrmico, arquitetura e urbanismo modelo adaptativo ashrae 55 (2004, 2010, 2013) aut0276 desempenho tÉrmico,

AUT0276 DESEMPENHO TÉRMICO, ARQUITETURA E URBANISMO

Evolução da ASHRAE 55 ASHRAE 55 – histórico

Page 18: Clima e Conforto térmico - fau.usp.br - Aula... · aut0276 desempenho tÉrmico, arquitetura e urbanismo modelo adaptativo ashrae 55 (2004, 2010, 2013) aut0276 desempenho tÉrmico,

AUT0276 DESEMPENHO TÉRMICO, ARQUITETURA E URBANISMO

PMV / PPD – Fanger (1970)

Page 19: Clima e Conforto térmico - fau.usp.br - Aula... · aut0276 desempenho tÉrmico, arquitetura e urbanismo modelo adaptativo ashrae 55 (2004, 2010, 2013) aut0276 desempenho tÉrmico,

AUT0276 DESEMPENHO TÉRMICO, ARQUITETURA E URBANISMO

Exemplo de aplicação: modelo adaptativo e o conceito de

temperatura efetiva para o Rio de Janeiro conforme ASHRAE

Report RP884

T e m p e ra tu ra s E fe tiva s d e C o n fo rto (tc ) - R J

1 8

2 0

2 2

2 4

2 6

2 8

3 0

3 2

0 7 3 0 1 4 6 0 2 1 9 0 2 9 2 0 3 6 5 0 4 3 8 0 5 1 1 0 5 8 4 0 6 5 7 0 7 3 0 0 8 0 3 0 8 7 6 0

H or a do a n o

Te

mp

era

tura

Efe

tiv

a (

°C)

Tc

90 % S u pe ri or

80 % S u pe ri or

90 % Infe ri or

80 % Infe ri or

zona de conforto nos ambientes naturalmente ventilados

Page 20: Clima e Conforto térmico - fau.usp.br - Aula... · aut0276 desempenho tÉrmico, arquitetura e urbanismo modelo adaptativo ashrae 55 (2004, 2010, 2013) aut0276 desempenho tÉrmico,

AUT0276 DESEMPENHO TÉRMICO, ARQUITETURA E URBANISMO

OT: Temperatura Operativa - (Winslow & Gagge, 1937)

To = (Tbs*hc + Trm*hr) / (hc+hr)

sendo:

Tbs = temp bulbo seco

Trm = temp radiante media

hc = coeficiente de troca convectiva

hr = coeficiente de troca radiativa

Page 21: Clima e Conforto térmico - fau.usp.br - Aula... · aut0276 desempenho tÉrmico, arquitetura e urbanismo modelo adaptativo ashrae 55 (2004, 2010, 2013) aut0276 desempenho tÉrmico,

AUT0276 DESEMPENHO TÉRMICO, ARQUITETURA E URBANISMO

MODELO ADAPTATIVO ASHRAE 55 (2004, 2010, 2013)

Page 22: Clima e Conforto térmico - fau.usp.br - Aula... · aut0276 desempenho tÉrmico, arquitetura e urbanismo modelo adaptativo ashrae 55 (2004, 2010, 2013) aut0276 desempenho tÉrmico,

AUT0276 DESEMPENHO TÉRMICO, ARQUITETURA E URBANISMO

Referências

ASHRAE (American Society of Heating, Refrigerating and Air Conditioning Engineers). Handbook of fundamentals. Atlanta, ASHRAE, 2013.

ASHRAE (American Society of Heating, Refrigerating and Air Conditioning Engineers). ASHRAE 55-2004 Thermal Environmental Conditions for Human Occupancy. Atlanta: ASHRAE, 2004.

ASHRAE (American Society of Heating, Refrigerating and Air Conditioning Engineers). ASHRAE 55-2013 Thermal Environmental Conditions for Human Occupancy. Atlanta: ASHRAE, 2013.

Belding, H S; Hatch, T F (1955), Index for evaluating heat stress in terms of resulting physiological strain. Heating, Piping, Air Conditioning, 27, pp 129-142.

Blazejczyk, Krysztof. Menex 2002. http://www.igipz.pan.pl/klimat/blaz/menex.htm. 2002a. Visited on 04/24/2004.

Bluestein, M; Osczevski, R (2002), Wind chill and the development of frostbite in the face. 15th Conf. on Biomet. and Aerobiology, Kansas City, MO, Amer. Meteor. Soc., pp 168-171, 2002.

Brown, Robert D; Gillespie, Terry J (1995), Microclimatic landscape design: creating thermal comfort and energy efficiency. New York, John Wiley & Sons.

Candido, C; de Dear, R. From thermal boredom to thermal pleasure: a brief literature review. Ambiente Construído, Porto Alegre, v.12, n.1, p.81-90, jan./mar. 2012

Candido, Chisthina, Lamberts, Roberto, de Dear, Richard, Bittencourt, Leonardo, VECCHI, Renata de. Towards a Brazilian standard for naturally ventilated buildings: guidelines for thermal

and air movement acceptability. Building Research & Information. Londres: Routledge, v. 39, n.2, 145–153, 2011.

CEN BRITISH STANDARD (BS) EN 15251: Indoor environmental input parameters for design and assessment of energy performance of buildings addressing indoor air quality, thermal

environment, lighting and acoustics. London, 2007.

Dominguez et al. (1992), Control climatico en espacios abiertos: el proyecto Expo'92. Sevilla, Universidad de Sevilla.

Gagge, A P; Stolwijk J A J; Hardy, J D (1967), Comfort and thermal sensations and associated physiological responses at various temperatures. Environ. Res., 1, pp 1-20.

Givoni, Baruch (1969), Man, climate and architecture. New York, John Wiley & Sons.

Givoni, Baruch; Noguchi, Mikiko (2002), Issues in outdoor comfort research. Passive and Low Energy Architecture, 17, Cambridge. Proceedings... London, J&J, pp 562-565, 2000.

Heshong, Lisa. Thermal Delight in Architecture. Cambridge, Massachusetts: The MIT Press, 1979.

Höppe, Peter R (1999), The physiological equivalent temperature: a universal index for the biometeorological assessment of the thermal environment. International Journal of Biometeorology,

43, pp 71-75.

Houghten, F C; Yaglou, C P (1923), Determining lines of equal comfort. ASHVE Trans. 29.

International Organization Standardization (ISO). ISO 7730. Ergonomics of the thermal environment: analytical determination and interpretation of thermal comfort using calculation of the PMV

and PPD indices and local thermal comfort criteria. Genève: ISO, 2005.

International Organization Standardization. ISO 7933. Hot environments: analytical determination and interpretation of thermal stress using calculation of required sweat rate. Genève, ISO,

1989.

Jendritzky, Gerd et al. (1979), Klimatologische Probleme – ein einfaches Verfahren zur Vorhersage der Wärmebelastung, in Zeitschrift für angewandte Bäder und Klimaheilkunde. Freiburg.

Masterton, J M; Richardson, F A (1979), Humidex: a method of quantifying human discomfort due to excessive heat and humidity. Environment Canada, CLI 1-79. Ontario, Downsview,

Atmospheric Environment Service.

McAriel, B et al. (1947), The prediction of the physiological effect of warm and hot environments, Med. Res. Council, 47, London.

Ministério do Trabalho (Brasil) (1978), NR15 Atividades e operações insalubres, Anexo 3 - Limites e tolerância para exposição ao calor. Brasília, Ministério do Trabalho.

Monteiro, L. M. Modelos preditivos de conforto térmico em espaços abertos. São Paulo: FAUUSP, 2008.

Nicol, Fergus. Standards for thermal comfort. Indoor air temperature standards for the 21st century. London: Taylor & Francis, 2006.

Nicol, J. Fergus. Adaptative comfort. Building Research & Information. Londres: Routledge, v.39, n. 2, p. 105-107, 2008.

Nikolopoulou, Marialena (org) (2004), Designing Open Spaces in the Urban Environment: a Bioclimatic Approach. Atenas, CRES.

Siple, P A; Passel, C F (1945), Measurements of dry atmospheric cooling in subfreezing temperatures. Proceedings of the American Philosophical Society, Vol. 89, No. 1, pp 177-199.

Webb, C, Thermal discomfort in an equatorial climate. Journal of the IHVE, 27, p 10.

Yaglou, C P; Minard, D (1957), Control of heat casualties at military training centers. A.M.A. Archives of Industrial Health, 16, pp 302-16.

Page 23: Clima e Conforto térmico - fau.usp.br - Aula... · aut0276 desempenho tÉrmico, arquitetura e urbanismo modelo adaptativo ashrae 55 (2004, 2010, 2013) aut0276 desempenho tÉrmico,

AUT0264 CONFORTO AMBIENTAL IV – TÉRMICA

1

caracterizar

ambiente

2

calcular

balanço térmico

3

calcular

fator de inércia

4

avaliar

conforto

5

verificar

ventilação

∆t (var.1)

OT

m (var.2)

N’

CONFORTO

NÃO

>N

<N

fazer

alterações

N, Or, A, k

2.1 ganhos [W (Ig)]

2.2 perdas [W ∆t]

∆t (var.1)

m (var.2)

Tme (var.3)

E (var.4)

Renovação: N (adotar)

Uso: Ocup/ lum/ Eq

Orientação: N, NE, E...

Materiais: A (m2)

Coeficiente: K

Ef. Chaminé:

Ae/s, H, ∆t, m

Ef. Ventos:

Ae/s, v, ce/s

Conjugado

fazer

alterações

Ae/s, H

Page 24: Clima e Conforto térmico - fau.usp.br - Aula... · aut0276 desempenho tÉrmico, arquitetura e urbanismo modelo adaptativo ashrae 55 (2004, 2010, 2013) aut0276 desempenho tÉrmico,

AUT0264 CONFORTO AMBIENTAL IV – TÉRMICA

Dados de clima (1) Média aritmética mensal

da temperatura em °C.

(2) Média mensal das temperaturas

máximas diárias em °C.

(3) Média mensal das temperaturas

mínimas diárias em °C.

(4) Temperatura máxima observada

no mês (média) em °C

(5) Temperatura mínima observada

no mês (média) em °C.

(6) Média aritmética mensal

da umidade relativa em %.

(7) Total mensal da chuva caída

(precipitação) em mm.

Fontes:

INMET (1984, 1992) e outras.

Page 25: Clima e Conforto térmico - fau.usp.br - Aula... · aut0276 desempenho tÉrmico, arquitetura e urbanismo modelo adaptativo ashrae 55 (2004, 2010, 2013) aut0276 desempenho tÉrmico,

AUT0264 CONFORTO AMBIENTAL IV – TÉRMICA

Dados de clima (1) Média aritmética mensal

da temperatura em °C.

(2) Média mensal das temperaturas

máximas diárias em °C.

(3) Média mensal das temperaturas

mínimas diárias em °C.

(4) Temperatura máxima observada

no mês (média) em °C.

(5) Temperatura mínima observada

no mês (média) em °C.

(6) Média aritmética mensal

da umidade relativa em %.

(7) Total mensal da chuva caída

(precipitação) em mm.

Fontes:

INMET (1984, 1992) e outras.

Page 26: Clima e Conforto térmico - fau.usp.br - Aula... · aut0276 desempenho tÉrmico, arquitetura e urbanismo modelo adaptativo ashrae 55 (2004, 2010, 2013) aut0276 desempenho tÉrmico,

AUT0264 CONFORTO AMBIENTAL IV – TÉRMICA

Dados de clima

Determinar temperatura externa média (temed) e elongação (E)

Ts — máxima observada no mês mais quente (média máx absolutas) — coluna 4;

Td — média das máximas diárias do mês mais quente — coluna 2;

ts — mínima observada no mês mais quente (média mín absolutas) — coluna 5;

td — média das mínimas diárias do mês mais quente — coluna 3.

Temax = (Td + Ts) / 2 e Temin = (td + ts) / 2 => temed = (Temax + Temin) / 2

Amplitude: A = Temax-Temin => Elongação: E = A /2

Page 27: Clima e Conforto térmico - fau.usp.br - Aula... · aut0276 desempenho tÉrmico, arquitetura e urbanismo modelo adaptativo ashrae 55 (2004, 2010, 2013) aut0276 desempenho tÉrmico,

AUT0264 CONFORTO AMBIENTAL IV – TÉRMICA

Determinação das condições ambientais internas

1) Cálculo da temperatura interna máxima (timax)

timax = temed + (1−m).E + (1−m).Δt (°C)

2) Consideração da temperatura externa média (temed)

3) Verificação: está dentro da zona de conforto térmico?

4) Qual a porcentagem de satisfeitos?

timax = 22,8 + (0,4) . 6 + (0,4) . 14,2 = 30,8oC

temed = 22,8oC

Page 28: Clima e Conforto térmico - fau.usp.br - Aula... · aut0276 desempenho tÉrmico, arquitetura e urbanismo modelo adaptativo ashrae 55 (2004, 2010, 2013) aut0276 desempenho tÉrmico,

AUT0264 CONFORTO AMBIENTAL IV – TÉRMICA

MODELO ADAPTATIVO ASHRAE 55 (2004, 2010, 2013)

22,8

30,8

Page 29: Clima e Conforto térmico - fau.usp.br - Aula... · aut0276 desempenho tÉrmico, arquitetura e urbanismo modelo adaptativo ashrae 55 (2004, 2010, 2013) aut0276 desempenho tÉrmico,

AUT0264 CONFORTO AMBIENTAL IV – TÉRMICA

Determinação das condições ambientais internas

1) Cálculo da temperatura interna máxima (timax)

timax = temed + (1−m).E + (1−m).Δt (°C)

2) Consideração da temperatura externa média (temed)

3) Verificação: está dentro da zona de conforto térmico?

4) Qual a porcentagem de satisfeitos?

timax = 22,8 + (0,4) . 6 + (0,4) . 14,2 = 30,8oC

temed = 22,8oC

Não

< 80%

Page 30: Clima e Conforto térmico - fau.usp.br - Aula... · aut0276 desempenho tÉrmico, arquitetura e urbanismo modelo adaptativo ashrae 55 (2004, 2010, 2013) aut0276 desempenho tÉrmico,

AUT0264 CONFORTO AMBIENTAL IV – TÉRMICA

1

caracterizar

ambiente

2

calcular

balanço térmico

3

calcular

fator de inércia

4

avaliar

conforto

5

verificar

ventilação

∆t (var.1)

OT

m (var.2)

N’

CONFORTO

NÃO

>N

<N

fazer

alterações

N, Or, A, k

2.1 ganhos [W (Ig)]

2.2 perdas [W ∆t]

∆t (var.1)

m (var.2)

Tme (var.3)

E (var.4)

Renovação: N (adotar)

Uso: Ocup/ lum/ Eq

Orientação: N, NE, E...

Materiais: A (m2)

Coeficiente: K

Ef. Chaminé:

Ae/s, H, ∆t, m

Ef. Ventos:

Ae/s, v, ce/s

Conjugado

fazer

alterações

Ae/s, H